| Plan Review Notes For Permit 18100142 |
| Permit Number |
18100142 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-17 16:57:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, PROVIDE A PLAN WHICH SHOWS PROPOSED WORK. | | | APPLICATION INDICATES "DOORS & ROOF TILE REPLACEMENT". | | | THE PLAN SHOULD SHOW LOCATION OF DOORS PROPOSED TO BE | | | REPLACED. IT SHOULD ALSO INDICATE LOCATION AND SCOPE OF | | | ROOF TILES TO BE REPLACED. NOTE THAT NOT MORE THAN 25% | | | OF THE ROOF CAN BE REPAIRED; OTHERWISE A REROOF IS | | | REQUIRED, FBC EB 706.1.1. | | | | | | YOU CAN MARK UP A FLOOR PLAN TO SHOW THIS INFORMATION. | | | EXISTING PLANS FOR THE ENTIRE BUILDING ARE NOT REQUIRED | | | FOR THIS MINOR SCOPE OF WORK. | | | | | | 2. PROVIDE PRODUCT APPROVAL FOR THE DOORS, FBC B 1609. | | | | | | 3. ON THE TILE PRODUCT APPROVAL, INDICATE METHOD OF | | | ATTACHMENT. UPON REQUEST THIS CAN BE SUBMITTED WITH THE | | | ROOF SUB PERMIT APPLICATION. | | | | | | PLEASE CONTACT ME IF YOU NEED ASSISTANCE. | | | | | | | | | | | | | | | | | | |
|