| 2018-10-23 16:14:06 | SHUTTERS SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | FLORIDA PRODUCT APPROVAL FL17080-R2 IS NOT DESIGNED FOR |
| | STEEL FRAMED APPLICATION. NEED PRODUCT APPROVAL THAT IS |
| | DESIGNED FOR PROPOSED INSTALLATION. OR SITE SPECIFIC |
| | PROJECTS USING THIS PRODUCT APPROVAL SHALL BE SUBMITTED |
| | TO THE PRODUCT APPROVAL ENGINEER FOR REVIEW AS REQUIRED |
| | BY NOTE 12(D) ON SHEET 1 OF 13. IF USING THIS PRODUCT |
| | APPROVAL, THEN NEED THE APPROVAL OF THE PRODUCT |
| | APPROVAL ENGINEER OF RECORD. SEC. 107.2.1 CITY |
| | AMENDMENTS AND FAC 61G20-3.001. |
| | |
| | RESPONSE: |
| | A) TALKED TO BUILDING OFFICIAL. EVEN THOUGHT IT LOOKS |
| | LIKE THE NOTE IMPLIES TO SENT DRAWINGS TO THE P.E.D. |
| | ENGINEER. NO NEED TO SEND DRAWINGS TO PRODUCT APPROVAL |
| | ENGINEER OF RECORD. ENGINEER OF RECORD WILL BE THE |
| | ENGINEER PROVIDING THE SITE SPECIFIC INSTALLATION USING |
| | THIS PRODUCT APPROVAL. |
| | |
| | B) SITE SPECIFIC DRAWINGS NEED TO PROVIDE ALL THE SITE |
| | SPECIFIC INFORMATION, INCLUDING ALL THE INFORMATION |
| | SHOWN IN THE INSTALLATION SCHEDULE. NEED TO SPECIFY THE |
| | SPECIFIC SHUTTER MOUNTING CONDITION ("C4" IS NOT A |
| | MOUNTING CONDITION); SHUTTER GLASS SEPARATION; SHUTTER |
| | SPAN, EDGE DISTANCE, ANCHOR TYPE AND SPACING (TOP & |
| | BOTTOM). SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | NOTE: INFORMATION SHOWN ON THE INSTALLATION SCHEDULE |
| | AND THE SITE SPECIFIC DRAWINGS DON'T MATCH. CHECK |
| | OPENINGS SIZES, ANCHOR TYPE, ETC. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |