| 2019-03-26 14:38:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18100072 |
| | 3/26/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH |
| | CARE FACILITIES |
| | ASHRAE 170-2008 |
| | |
| | PLAN REVIEW RESULTS: DENIED: |
| | |
| | 1) THE ENGINEER'S RESPONSES TO COMMENT'S #4 & 5 FROM |
| | THE PREVIOUS REVIEW (PRINTED BELOW) MUST BE PUT INTO A |
| | SINGED AND ESA;LED LETTER FOR FINAL APPROVAL. |
| | |
| | 4) NEW PLAN SHEET M4.0: A) THE FIRE DAMPER IN THE MED |
| | GAS EXHAUST DUCT IS PROHIBITED- SECTION 510.7.1 FBC M. |
| | B) THE EXHAUST DUCT PENETRATING THE FIRE-RATED MED GAS |
| | ROOM WALL SHALL BE ENCLOSED IN FIRE-RATED CONSTRUCTION |
| | FROM THE POINT OF PENETRATION TO THE OUTLET TERMINAL- |
| | SECTION 510.7.3 FBC M. C) THE EXHAUST OUTLET FROM THE |
| | MED GAS ROOM SHALL HAVE A MINIMUM 10' CLEARANCE TO THE |
| | DOOR OPENING- SECTION 501.3.1 (2) FBC M. |
| | |
| | 5) SHEET M4.3 & M4.4: THE EXHAUST SYSTEM FOR THE |
| | ANESTHESIA ROOM SHALL BE INDEPENDENT OF THE OTHER |
| | ENVIRONMENTAL EXHAUST SYSTEMS- SEE SECTION 501.2 FBC M. |
| | |
| | 7) DEFERRED SUBMITTALS |
| | |
| | A) SUPPLY AND EXHAUST DUCTWORK. |
| | B) OR AND PROCEDURE ROOM DIFFUSERS AND GRILLES. |
| | C) DIFFERENTIAL PRESSURE SENSORS |
| | D) CHILLED WATER AND STEAM PIPING. |
| | E) PIPING INSULATION |
| | F) FILTER BANKS |
| | G) DUCT SMOKE DETECTORS |
| | H) FIRE AND FIRE/SMOKE DAMPERS |
| | |
| | PLEASE NOTE ALL SUBMITTALS MAY BE DEFERRED IN |
| | ACCORDANCE WITH SECTION 107.3.4.1 WPB. PROVIDE A LIST |
| | ON THE PLANS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | IF YOU HAVE ANY QUESTIONS ABOUT THE REVIEW COMMENTS |
| | PLEASE CONTACT ME. |
| | |