Plan Review Notes
Plan Review Notes For Permit 18100072
Permit Number 18100072
Review Stop M
Sequence Number 2
Notes
Date Text
2019-03-06 08:32:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18100072
 3/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH
 CARE FACILITIES
 ASHRAE 170-2008
  
 PLAN REVIEW RESULTS: DENIED:
  
 1) THE AC CALCULATIONS REQUIRE ELECTRONIC SEALS AND
 SIGNATURES PER SECTION 61G15-23.005 FAC.
  
 2) IN REFERENCE TO 1ST REVIEW COMMENT'S #8A, B, C, D,
 IT APPEARS THAT THE LS1.1 PLAN HAS NOT BEEN UPDATED TO
 REMOVE THE HAZARDOUS ROOM IDENTIFICATIONS- SEE COLOR
 LEGEND THAT DESIGNATES HATCHED AREAS AS "HAZARDOUS
 STORAGE".
  
 3) IN REFERENCE TO 1ST REVIEW COMMENT #8D, THE LS1.1
 PLAN IS STILL INDICATING ROOM 2083 AS "STERILE SUPPLY"
 HOWEVER THE NARRATIVE RESPONSE INDICATES THIS ROOM HAS
 BEEN CHANGED TO "CLEAN SUPPLY".
  
 4) NEW PLAN SHEET M4.0: A) THE FIRE DAMPER IN THE MED
 GAS EXHAUST DUCT IS PROHIBITED- SECTION 510.7.1 FBC M.
 B) THE EXHAUST DUCT PENETRATING THE FIRE-RATED MED GAS
 ROOM WALL SHALL BE ENCLOSED IN FIRE-RATED CONSTRUCTION
 FROM THE POINT OF PENETRATION TO THE OUTLET TERMINAL-
 SECTION 510.7.3 FBC M. C) THE EXHAUST OUTLET FROM THE
 MED GAS ROOM SHALL HAVE A MINIMUM 10' CLEARANCE TO THE
 DOOR OPENING- SECTION 501.3.1 (2) FBC M.
  
 5) SHEET M4.3 & M4.4: THE EXHAUST SYSTEM FOR THE
 ANESTHESIA ROOM SHALL BE INDEPENDENT OF THE OTHER
 ENVIRONMENTAL EXHAUST SYSTEMS- SEE SECTION 501.2 FBC M.
  
 6) M4.5: IN REFERENCE TO 1ST REVIEW COMMENT #9 PLEASE
 SHOW THE LOCATION OF THE REQUIRED DUCT SMOKE DETECTOR
 FOR THE NEW AHU-1- SECTION 606.2.1 FBC M.
  
 7) REQUIRED PRODUCT SUBMITTALS TO BE APPROVED BY THE
 ENGINEER OF RECORD:
  
 A) SUPPLY AND EXHAUST DUCTWORK.
 B) OR AND PROCEDURE ROOM DIFFUSERS AND GRILLES.
 C) DIFFERENTIAL PRESSURE SENSORS
 D) CHILLED WATER AND STEAM PIPING.
 E) PIPING INSULATION
 F) FILTER BANKS
 G) DUCT SMOKE DETECTORS
 H) FIRE AND FIRE/SMOKE DAMPERS
  
 PLEASE NOTE ALL SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION 107.3.4.1 WPB. PROVIDE A LIST
 ON THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 IF YOU HAVE ANY QUESTIONS ABOUT THE REVIEW COMMENTS
 PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  