Plan Review Notes
Plan Review Notes For Permit 18100072
Permit Number 18100072
Review Stop P
Sequence Number 1
Notes
Date Text
2019-01-08 09:30:071ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
 1. SHT. A9.2 DETAIL #8 THE CLEAR FLOOR SPACE FOR THE
 TOILET SHOWS THE SHOWER ENCROACHING INTO SPACE THE
 SHOWER IS NOT PERMITTED TO ENCROACH THE SHOWER STALL
 SHALL BE OUTSIDE OF THE CLEAR FLOOR SPACE. PER FBC ACC
 604.3.2
 2. SHT. A9.2 DETAIL #8 THE TRANSFER TYPE SHOWER SHALL
 HAVE WALLS ON THREE SIDES, ONE SIDE WALL WITH A SEAT, A
 BACK WALL WITH GRAB BARS AND ANOTHER SIDE WALL WITH
 CONTROLS. PER FBC ACC 608.2.1, FIGURE 608.2.1, 608.3.1,
 608.4
 3. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC
 ACC 608.5.1
 4. GRAB BARS SHALL BE INSTALLED 33 INCHES MINIMUM AND
 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO
 THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 909.4
 5. SHT P2.1 THE SHOWER IN THE MEN?S LOCKER ROOM
 BATHROOM #2111 IS SHOWN ENCROACHING INTO THE CLEAR
 FLOOR SPACE OF THE TOILET AND DOES NOT MATCH THE LAYOUT
 OF THE ARCHITECTURAL PLANS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. A1.1 SHOWS A CLINICAL SINK IN ROOM T2049 SHT
 P2.1 DOES NOT SHOW A CLINICAL SINK AND THE DEMO NOTES
 IT BEING REMOVED PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 7. SHT. A1.1 ROOM T2002 DOES NOT SHOW THE MOP SINK THAT
 IS SHOWN ON SHT P2.1 PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
 8. SHT. P2.1 THE (X)1 ??DHW FOR THE MEN?S LOCKER ROOM
 BATHROOM SHALL BE RECONNECTED TO THE (X) ?? DHR AS IT
 WAS REMOVED ON THE DEMO SHEET P1.1. PER FBC PL 607.2
 9. PLEASE PROVIDE A SANITARY FLOOR PLAN SHOWING NEW AND
 EXISTING PIPING AND LABEL THE STACK TO MATCH LABELS ON
 THE ISOMETRIC DRAWINGS . PER WPB AMEND TO FBC 107.2.1
 10. SHT. P3.1 THE ISOMETRIC ON STACK B-1 WITH THE NURSE
 STATION 2002 SHOWS A S1 I COULD NOT LOCATE ON THE FLOOR
 PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 11. SHT. P3.1 THE ISOMETRIC ON STACK B-1 WITH THE NURSE
 STATION 2002 IS SHOWING A FIXTURE LABEL W3 PLEASE
 IDENTIFY THIS FIXTURE PROVIDE A FIXTURE SCHEDULE. . PER
 WPB AMEND TO FBC 107.2.1
 12. SHT. P3.1 I COULD NOT LOCATE THE NEW PIPING FOR THE
 MOP SINK IN JANITORS ROOM T2002 PLEASE CLARIFY. . PER
 WPB AMEND TO FBC 107.2.1
 13. SHT. P3.2 PLEASE LABEL ALL HOT AND COLD PIPING. .
 PER WPB AMEND TO FBC 107.2.1
 14. SHT. P3.2 THE NEW LINE NPSW FROM THE WATER SOFTNER
 DOES NOT MATCH THE LAY OUT FROM THE FLOOR PLAN SHT.
 P2.1 PLEASE CLARIFY. . PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]