| 2019-01-08 09:30:07 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | 1. SHT. A9.2 DETAIL #8 THE CLEAR FLOOR SPACE FOR THE |
| | TOILET SHOWS THE SHOWER ENCROACHING INTO SPACE THE |
| | SHOWER IS NOT PERMITTED TO ENCROACH THE SHOWER STALL |
| | SHALL BE OUTSIDE OF THE CLEAR FLOOR SPACE. PER FBC ACC |
| | 604.3.2 |
| | 2. SHT. A9.2 DETAIL #8 THE TRANSFER TYPE SHOWER SHALL |
| | HAVE WALLS ON THREE SIDES, ONE SIDE WALL WITH A SEAT, A |
| | BACK WALL WITH GRAB BARS AND ANOTHER SIDE WALL WITH |
| | CONTROLS. PER FBC ACC 608.2.1, FIGURE 608.2.1, 608.3.1, |
| | 608.4 |
| | 3. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC |
| | ACC 608.5.1 |
| | 4. GRAB BARS SHALL BE INSTALLED 33 INCHES MINIMUM AND |
| | 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO |
| | THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 909.4 |
| | 5. SHT P2.1 THE SHOWER IN THE MEN?S LOCKER ROOM |
| | BATHROOM #2111 IS SHOWN ENCROACHING INTO THE CLEAR |
| | FLOOR SPACE OF THE TOILET AND DOES NOT MATCH THE LAYOUT |
| | OF THE ARCHITECTURAL PLANS PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 6. SHT. A1.1 SHOWS A CLINICAL SINK IN ROOM T2049 SHT |
| | P2.1 DOES NOT SHOW A CLINICAL SINK AND THE DEMO NOTES |
| | IT BEING REMOVED PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 7. SHT. A1.1 ROOM T2002 DOES NOT SHOW THE MOP SINK THAT |
| | IS SHOWN ON SHT P2.1 PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | 8. SHT. P2.1 THE (X)1 ??DHW FOR THE MEN?S LOCKER ROOM |
| | BATHROOM SHALL BE RECONNECTED TO THE (X) ?? DHR AS IT |
| | WAS REMOVED ON THE DEMO SHEET P1.1. PER FBC PL 607.2 |
| | 9. PLEASE PROVIDE A SANITARY FLOOR PLAN SHOWING NEW AND |
| | EXISTING PIPING AND LABEL THE STACK TO MATCH LABELS ON |
| | THE ISOMETRIC DRAWINGS . PER WPB AMEND TO FBC 107.2.1 |
| | 10. SHT. P3.1 THE ISOMETRIC ON STACK B-1 WITH THE NURSE |
| | STATION 2002 SHOWS A S1 I COULD NOT LOCATE ON THE FLOOR |
| | PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | 11. SHT. P3.1 THE ISOMETRIC ON STACK B-1 WITH THE NURSE |
| | STATION 2002 IS SHOWING A FIXTURE LABEL W3 PLEASE |
| | IDENTIFY THIS FIXTURE PROVIDE A FIXTURE SCHEDULE. . PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 12. SHT. P3.1 I COULD NOT LOCATE THE NEW PIPING FOR THE |
| | MOP SINK IN JANITORS ROOM T2002 PLEASE CLARIFY. . PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 13. SHT. P3.2 PLEASE LABEL ALL HOT AND COLD PIPING. . |
| | PER WPB AMEND TO FBC 107.2.1 |
| | 14. SHT. P3.2 THE NEW LINE NPSW FROM THE WATER SOFTNER |
| | DOES NOT MATCH THE LAY OUT FROM THE FLOOR PLAN SHT. |
| | P2.1 PLEASE CLARIFY. . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |