Plan Review Notes
Plan Review Notes For Permit 18100072
Permit Number 18100072
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-20 11:15:31****CORRECTIONS****
 W.P.B. PERMIT: 18100072
 REVIEWED: DECEMBER 17, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2. [FBC 107.3.5]PROVIDE SITE PLAN TO SHOW PROPERTY
 BOUNDARIES AND DISTANCES FROM PROPERTY LINE.
  
 3. [FBC EXISTING 501]SHEET A0.0-IN BUILDING DATA, STATE
 THE LEVEL OF ALTERATION FOR WORK BEING PERFORMED. THIS
 WOULD APPEAR TO BE A LEVEL 2 ALTERATION.
  
 4. [FBC 107.3.5]SHEET LS1.1
 A) IN EGRESS CALCULATIONS 2ND FLOOR. WHERE COLUMN D
 ADDS UP AREAS 2A AND 2B, THE TOTAL BELOW SAYS 12,233.
 PLEASE CHECK HOW COLUMN ABOVE ADDS UP BECAUSE IT SHOULD
 BE 21,233 (LOOKS LIKE FIRST TWO DIGITS GOT REVERSED)
 B) UPDATE CODE SECTIONS IN ALLOWABLE TRAVEL DISTANCES.
 TABLE 1017.2 FOR TRAVEL DISTANCES AND 1020.4 FOR DEAD
 END CORRODORS.
 C) WHAT IS BEING STORED IN STORAGE 2003, 2090 & 2101
 THAT IS LABLED HAZARDOUS AREA AND WHAT TYPES/AMOUNTS OF
 HAZARDOUS MATERIALS ARE STORED?
 D) WHAT IS BEING STORED IN STORAGE ROOM NEXT TO EXAM
 RM#14 T2022?
 THERE IS NO ROOM DESIGNATION FOR THIS STORAGE ROOM.
 E) ARE MEDGAS CONTAINERS STORED ON THIS FLOOR AND WHERE
 DO MEDGAS LINES ORIGINATE?
  
 5. [FBC 451.3.4.1]NO DOORS SHALL SWING INTO THE
 CORRIDOR EXCEPT
 THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR
 ELECTRICAL
 ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH THE DOORS
 IN THE CLOSED POSITION.
 DOOR T2026 1.3-1.N SHOULD BE REVIEWED FOR CODE
 COMPLIANCE WITH 451.3.4.1.
  
 6. [FBC 107.3.5]SHEET A1.1
 A) KEYNOTE #1 REFERS TO SEE SHEET A0.2. IS THIS
 SUPPOSED TO BE SHEET A0.3 FOR UL DETAILS?
 B) THERE IS A SMOKE BARRIER WITH NOTES TO INSTALL RATED
 WALL. CAN A CALL OUT BE ADDED TO SHOW DETAIL OF HOW
 THIS WALL COMPLIES WITH 709.4 CONTINUITY.
 C) CHECK THAT ALL NEW WALLS HAVE WALL TYPE ACCOCIATED
 WITH IT.
  
 7. [FBC TABLE 716.5]DEMO PLAN SHOWS DOORS BEING
 REMOVED. SHEET A7.1 HAS DOOR SCHEDULE, BUT LITTLE
 INFORMATION PROVIDED.
 PLEASE PROVIDE DOOR TYPES TO INCLUDE DOOR RATINGS AT
 RATED WALLS AND SMOKE BARRIER.
  
 8. [FBC 803.4]BENCHES. A BENCH COMPLYING WITH 903 SHALL
 BE PROVIDED WITHIN THE ROOM.
 CHECK BOTH LOCKER ROOMS FOR COMPLIANCE WITH FBC
 ACCESSIBILITY WHERE NEW WORK IS OCCURING.
  
 9. [FBC A404.2.4]MANEUVERING CLEARANCES.
 A) ACCESSIBLE BATHROOMS STALLS IN LOCKER ROOMS ARE
 GOOD, BUT THE TWO DOORS LEADING INTO LOCKER ROOMS
 SHOULD BE REVIEWED FOR COMPLIANCE WITH MANEUVERING
 CLEARANCE. WHILE I UNDERSTAND THAT SOME WORK IS
 EXISTING TO REMAIN, THIS AREA IS BEING SUBSTANTIALLY
 REWORKED AND THE NEW STALLS SHOULD BE FULLY ACCESSIBLE.
 B) PLEASE UPDATE DOOR SCHEDULE TO STATE DOOR TYPES AND
 IF DOOR CLOSERS ARE PROVIDED.
 C) CHECK THAT MANEUVERING CLEARANCES WORK AT EACH NEW
 WORK AREA WITH THE DOOR SCHEDULE.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  