2018-10-18 15:20:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E9-20, NOTE 1 CALLS FOR A 60KW DIESEL GENSET
 WHICH CORRESPONDS WITH SPEC SHEET PROVIDED FOR
 GENERATOR. SHEET E9-30 AND E9-40 CALL FOR A 50KW
 GENSET. CORRECT DISCREPANCY. WPB FBC 107.2.1
 2. THE ADDRESS ON PLANS NEEDS TO BE CLARIFIED. THIS
 PERMIT APPLICATION IS FOR 101 EXECUTIVE CENTER DR.,
 WHILE PERMIT APPLICATION 18100064 IS FOR 111 EXECUTIVE
 CENTER DR.. EITHER PROVIDE BOTH ADDRESSES ON PLAN SET,
 OR SUBMIT SEPARATE PLAN FOR EACH ADDRESS. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  