| 2018-10-18 15:20:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET E9-20, NOTE 1 CALLS FOR A 60KW DIESEL GENSET |
| | WHICH CORRESPONDS WITH SPEC SHEET PROVIDED FOR |
| | GENERATOR. SHEET E9-30 AND E9-40 CALL FOR A 50KW |
| | GENSET. CORRECT DISCREPANCY. WPB FBC 107.2.1 |
| | 2. THE ADDRESS ON PLANS NEEDS TO BE CLARIFIED. THIS |
| | PERMIT APPLICATION IS FOR 101 EXECUTIVE CENTER DR., |
| | WHILE PERMIT APPLICATION 18100064 IS FOR 111 EXECUTIVE |
| | CENTER DR.. EITHER PROVIDE BOTH ADDRESSES ON PLAN SET, |
| | OR SUBMIT SEPARATE PLAN FOR EACH ADDRESS. WPB FBC |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |