| 2018-12-10 15:30:09 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | 1) THE INSTALLATION OF THE GENERATOR SHALL COMPLY WITH |
| | THE REQUIRMENTS OF NFPA 37. |
| | |
| | PER NFPA 1, CHAPTER 11, BUILDING SERVICES |
| | |
| | 11.7 STATIONARY GENERATORS AND STANDBY POWER SYSTEMS |
| | 11.7.1 11.7.1 STATIONARY COMBUSTION ENGINES AND GAS |
| | TURBINES |
| | INSTALLATION. STATIONARY GENERATOR SETS SHALL BE |
| | INSTALLED IN |
| | ACCORDANCE WITH NFPA 37, STANDARD FOR THE INSTALLATION |
| | AND USE |
| | OF STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| | NFPA 70. |
| | |
| | |
| | |
| | 2) ANY PROPOSED TIE IN TO THE FIRE ALARM AND/OR FIRE |
| | SPRINKLER SYSTEM SHALL BE DONE UNDER SEPARATE SHOP |
| | DRAWINGS UNDER APPLICABLE NFPA CODES. |
| | |
| | |
| | 3) TIE IN TO ANY LIFE SAFETY SYSTEMS OR AS PER |
| | APPLICABLE LAW SHALL BE UNDER NFPA 110 |
| | |
| | 11.7.3 EMERGENCY AND LEGALLY REQUIRED STANDBY POWER |
| | SYSTEMS. |
| | 11.7.3.1 GENERAL. NEW STATIONARY GENERATORS FOR |
| | EMERGENCY USE |
| | OR FOR LEGALLY REQUIRED STANDBY POWER REQUIRED BY THIS |
| | CODE, THE |
| | BUILDING CODE, OR OTHER CODES AND STANDARDS SHALL BE |
| | INSTALLED IN |
| | ACCORDANCE WITH NFPA 110, STANDARD FOR EMERGENCY AND |
| | STANDBY |
| | POWER SYSTEMS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |