Plan Review Notes
Plan Review Notes For Permit 18100051
Permit Number 18100051
Review Stop P
Sequence Number 1
Notes
Date Text
2018-11-05 06:57:00PROVISO:
 1. FLOOR DRAIN NOT PERMITTED IN ENCLOSED SPACE SUCH AS
 WALL CAVITY OR CLOSET. PER FBC PL 802.3 REMOVE TERM
 FLOOR DRAIN AND REPLACE WITH STANDPIPE ABOVE FLOOD
 LEVEL RIM OF PLUMBING FIXTURES IN BATHROOM. WPB AMEND
 TO FBC 107.2.1
 2. PROVIDE A DETAIL FOR THE STANDPIPE THAT WILL RECEIVE
 THE DRAINAGE FROM THE STEAM GENERATOR AS PER DISCUSSION
 WITH ENGINEER OF RECORD ADRIAN RAJKUMAR. WPB AMEND TO
 FBC 107.2.1
  