| Plan Review Notes For Permit 18100037 |
| Permit Number |
18100037 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-04 09:48:27 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-2 | | | | | | RISER SHOW 1/0 AL WITH 150A MAIN, CONDUCTORS ARE ONLY | | | GOOD FOR 125A PER CODE. 310.15(B)(16). | | | | | | #8 FEEDING THE 60A BREAKER ? | | | | | | YOUR CALCULATION SHOWS THE #8 AT 75 AMPERES? | | | 310.15(B)(16) SHOWS 55 AMPERES? | | | | | | | | | | | | |
|