| 2018-12-06 16:50:44 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18091312 |
| | 12/6/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) M101 & M102: SHOW THE LOCATIONS OF ACCESS PANELS FOR |
| | SERVICE AND REPLACEMENT OF ANY VAV BOXES LOCATED ABOVE |
| | HARD CEILINGS- SECTION 306.1 FBC M. PLEASE INCLUDE THE |
| | DIMENSIONS OF THE PANELS |
| | |
| | 2) SHEET S103 & M103: A) THE TYP. MECH.UNIT ATTACHMENT |
| | DETAIL IS MISSING THE RTU ATTACHMENT TO THE 12 GA. |
| | ANGLE. B) EXHAUST FAN CURB ATTACHMENT DETAIL MISSING |
| | FAN TO CURB ATTACHMENT. IF THE FAN HAS FLORIDA PRODUCT |
| | OR MIAMI-DADE NOA APPROVAL, PLEASE PROVIDE THE |
| | DOCUMENT. C) ENGINEERING FOR INSTALLATION OF THE |
| | ROOFTOP DUCTWORK NOT PROVIDED. PROVIDE DETAILS |
| | INDICATING HOW THE DUCTWORK WILL BE SUPPORTED AND |
| | ATTACHED TO THE ROOF STRUCTURE. D) STEEL DUNNAGE |
| | ATTACHMENT TO THE ROOF STRUCTURE NOT PROVIDED. |
| | |
| | 3) M103: INDICATE THE TYPE AND GAGE OF ROOFTOP DUCTWORK |
| | TO BE INSTALLED, AND THE INSULATION R-VALUE. |
| | |
| | 4) EN-001: THE COMCHECK COMPLIANCE REPORT IS MISSING |
| | THE DATA FOR THE AC-3 & 4 MITSUBISHI SYSTEMS. |
| | |
| | 5) THE SUMMARY AC CALCULATIONS UPLOADED ARE MISSING THE |
| | PROJECT ADDRESS, THE OUTDOOR WET AND DRY BULB |
| | TEMPERATURES USED, AND THE INDOOR DRY BULB TEMPERATURE |
| | USED. |
| | |
| | |
| | ]WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |