| Date |
Text |
| 2018-12-06 09:05:03 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED. |
| | SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE, |
| | AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR |
| | APPROVAL.) |
| | 9. CORRECTED. |
| | 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL |
| | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED |
| | DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES |
| | NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5, |
| | 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR |
| | APPROVAL.) |
| | 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 (NOT PROVIDED, REQUIRED FOR APPROVAL. |
| | A DEFERRED SUBMITTAL IS ACCEPTABLE IF RESPONSE FROM FPL |
| | IS DELAYED. HOWEVER, BE ADVISED THAT THE CONTRACTOR IS |
| | PROCEEDING AT HIS OWN RISK. IF THIS IS DESIRED, PROVIDE |
| | BLOCK NOTE ON PLAN THAT THIS INFORMATION WILL BE |
| | PROVIDED PRIOR TO FIRST INSPECTION.) |
| | 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| | PANELS. NEC 110.3, 110.9 (NOT PROVIDED, REQUIRED FOR |
| | APPROVAL. A DEFERRED SUBMITTAL IS ACCEPTABLE IF |
| | RESPONSE FROM FPL IS DELAYED. HOWEVER, BE ADVISED THAT |
| | THE CONTRACTOR IS PROCEEDING AT HIS OWN RISK. IF THIS |
| | IS DESIRED, PROVIDE BLOCK NOTE ON PLAN THAT THIS |
| | INFORMATION WILL BE PROVIDED PRIOR TO FIRST |
| | INSPECTION.) |
| | 13. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |