| 2018-10-24 17:45:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18091312 |
| | 10/24/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 3) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR |
| | THE O/A INTAKE DUCTS- SECTION C403.2.4.3 FBC-17 ENERGY |
| | CONSERVATION. |
| | |
| | 4) SHEET M-501.00: PROVIDE DUCT HANGING AND CONNECTION |
| | DETAILS PER SMACNA HVAC DUCT CONSTRUCTION |
| | STANDARDS-2005. THE DUCT DETAILS AND HANGER TABLE SHOWN |
| | ON THE PLANS ARE NOT IN COMPLIANCE, AND ARE BASED ON A |
| | NYC CODE. |
| | |
| | 5) M501: PROVIDE A HORIZONTAL FIRE DAMPER INSTALLATION |
| | DETAIL PER MANUFACTURER'S SPECIFICATIONS AND SUBMIT THE |
| | SPECS FOR THE DEVICE- SECTION 607.5.2 FBC M. INDICATE |
| | HOW ACCESS WILL BE PROVIDED TO THE DAMPERS IN THE |
| | SUPPLY AND RETURN RISERS- SECTION 607.4 FBC M. |
| | |
| | 6) M101: REQUIRED RETURN AIR FROM THE SECURITY- IT ROOM |
| | NOT SHOWN. |
| | |
| | 7) M102: REQUIRED RETURN AIR FROM THE BREAKROOM NOT |
| | SHOWN. |
| | |
| | 8) M102: CLARIFY IF ANY COOKING APPLIANCES OR EXHAUST |
| | HOOD SYSTEMS WILL BE INSTALLED IN THE BREAKROOM OR |
| | STAFF LOUNGE, AND PROVIDE DETAILS, SPECIFICATIONS, AND |
| | PRODUCT SUBMITTALS IF APPLICABLE. PLEASE NOTE THAT |
| | SEPARATE PERMITS ARE REQUIRED FOR KITCHEN EXHAUST HOODS |
| | AND FIR SUPPRESSION SYSTEMS. |
| | |
| | 9) M102: THE CONDENSATE DRAINING INTO THE MOP SINK IS |
| | PROHIBITED PER SECTION 90-126 WPB CODE OF ORDINANCES |
| | |
| | 10) M103: COMPLETE WIND LOAD ENGINEERING IS REQUIRED |
| | FOR THE RTU'S, ROOFTOP CONDENSER UNITS AND STANDS, AND |
| | THE EXHAUST FAN AND CURB- SECTION 301.15. PLEASE NOTE |
| | THE RTU DETAIL ON S-400 IS INCOMPLETE- RTU ATTACHMENT |
| | TO CURB NOT SHOWN AND NO DESIGN CRITERIA HAS BEEN |
| | PROVIDED. |
| | |
| | 11) M103: SHOW HOW ACCESS IS BEING PROVIDED TO THE |
| | EQUIPMENT ON THE ROOF- SEE SECTION 306.5 FBC M. |
| | |
| | 12) M103: VERIFY THE REQUIRED 10' REQUIRED CLEARANCE |
| | FOR THE SERVICEABLE ROOF TOP MECHANICAL EQUIPMENT TO |
| | THE ROOF EDGES OR VERIFY 42" GUARD OR PARAPET IN PLACE- |
| | SECTION 304.11 FBC M. |
| | |
| | 13) THE PROPOSED PROJECT IS CLASSIFED AS A"RENOVATED |
| | BUILDING" PER SECTION 202 FBC EC. PLEASE SUBMIT AN |
| | ENERGY COM[PLIANCE REPORT IN ACCORDANCE WITH SECTIONS |
| | C101.5.1 & C101.5.1.1 FBC EC. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |