| 2018-10-12 12:55:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1 SHEET LS 101 - THERE IS AN INCORRECT REFERNECE TO THE |
| | CURRENT FLORIDA FIRE PREVENTION CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND |
| | ALL OTHER APPLICABLE CODES OR STANDARDS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE WERE APPLICABLE AND |
| | PROVIDE A CORRECTION. |
| | |
| | |
| | |
| | |
| | 2) SHEET E 101 - THERE DOES NOT APPEAR TO BE AN EXIT |
| | SIGN AT DOOR 108 INSIDE THE PROCESSING ROOM. |
| | |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | |
| | AN EXIT SIGN IS REQUIRED ABOVE THAT DOOR. |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY |
| | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| | REACH THE EXIT IS |
| | NOT READILY APPARENT TO THE OCCUPANTS. |
| | |
| | AN EXIT SIGN IS REQUIRED AT THE END WALL LEADING TO THE |
| | EXIT DOOR. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 3) SHEET E 101 - THERE DOES NOT APPEAR TO BE AN EXIT |
| | SIGN AT DOOR 103 ON THE.SALES ROOM SIDE. |
| | |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | |
| | AN EXIT SIGN IS REQUIRED ABOVE THAT DOOR. |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY |
| | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO |
| | REACH THE EXIT IS |
| | NOT READILY APPARENT TO THE OCCUPANTS. |
| | |
| | AN EXIT SIGN IS REQUIRED IN THE SALES ROOM OPEN AREA |
| | LEADING TO THE EXIT DOOR. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 101 - DOOR 107 IS INDICATED AS OPENING OUT |
| | INTO THE EXIT ACCESS CORRIDAR. |
| | |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS |
| | |
| | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, |
| | UNLESS BOTH |
| | OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE |
| | REQUIRED WIDTH |
| | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, |
| | UNLESS THE DOOR |
| | LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE |
| | AND IS NOT |
| | REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE |
| | DIRECTION OF |
| | EGRESS TRAVEL. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | 5) CS 1.00 - THERE IS AN INDICATION UNDER PREFIX 029 |
| | THAT THE DOOR SCHEDULE AND HARWARE SET ARE ON SHEET A |
| | 810. |
| | |
| | SHEET A 810 DOES NOT DIPLAY THAT INFORMATION AND THE |
| | DOOR SCHULE AND HARDWARE SET INFORMATION COULD NOT BE |
| | LOCATED. |
| | |
| | THE HARDWARE ON THE EXIT DOES COULD NOT BE VERIFIED OR |
| | CONFIRMED TO BE CODE COMPLIANT PER NFPA 101, CHAPTER 7 |
| | MEANS OF EGRESS. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 6) SHEET A 131 - THERE ARE INDICATIONS OF ACCESS |
| | CONTROL AT EXIT DOORS. ALL ACCESS CONTROL SHALL COMPLY |
| | WITH PER NFPA 101, CHAPTER 7 MEANS OF EGRESS |
| | |
| | ACCESS CONTROL SHALL BE SUBMITTED UNDER SEPARATE SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT AND COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |