| 2018-11-15 08:07:37 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18091312 |
| | REVIEWED: NOVEMBER 14, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | CURRENT CODES: |
| | ADOPTED DECEMBER 31, 2017 |
| | FLORIDA BUILDING CODE(FBC), 6TH EDITION (2017) |
| | |
| | 1. [FBC 107.3.5]UPDATE SHEETS LS-101 AND LS102 FOR |
| | CURRENT DODE EDITIONS. |
| | |
| | 2. [FBC 107.3.5]THIS SHOULD BE A LEVEL 3 ALTERARTION |
| | SINCE IT AFFECTS MORE THAN 50% OF THE BUILDING. |
| | PLEASE UPDATE LS-101 AND LS102 TO STATE LEVEL 3 |
| | ALTERATION. |
| | |
| | 3. [FBC TABLE 1004.1.2]SHEETS LS-101 AND LS102 SHOW |
| | FIRST FLOOR OCCUPANT LOAD FOR MERCANTILE AT 30 SQ. FT. |
| | PER. |
| | MERCANTILE WOULD BE CALCULATED AT 60 SQ. FT. PER PERSON |
| | LIKE SHOWN FOR SECOND FLOOR. |
| | PLEASE REVISE OCCUPANT COUNT TO REFLECT MERCANTILE PER |
| | TABLE 1004.1.2. |
| | |
| | 4. [FBC 1015.7]ROOF ACCESS. GUARDS SHALL BE PROVIDED |
| | WHERE THE ROOF |
| | HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 MM) OF A |
| | ROOF |
| | EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR |
| | OPEN |
| | SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| | FLOOR, |
| | ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO |
| | AS TO |
| | PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN |
| | DIAMETER. |
| | VERIFY THAT PARAPET PROVIDES EDGE PROTECTION OR ADD |
| | RAIL TO MEET FBC 1015. |
| | -PROVIDE PRODUCT APPROVAL FOR NEW ROOF HATCH. |
| | |
| | 5. [FBC 1510.10]MECHANICAL UNITS. ROOF MOUNTED |
| | MECHANICAL UNITS |
| | SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES |
| | (203 |
| | MM) ABOVE THE ROOF SURFACE. |
| | PROVIDE DETAIL OF NEW HVAC EQUIPMENT CURBS. STRUCTURAL |
| | SHEET S-201 SAYS SEE MECHANICAL AND MECHANICAL M-103 |
| | SAYS SEE STRUCTURAL FOR ATTACHMENT. |
| | |
| | 6. [FBC 107.3.5]SHEET A-801 AND SHEET A-810 ARE |
| | REVERSED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |