| 2019-09-18 12:57:47 | 3RD REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | |
| | MED GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH |
| | |
| | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE VACUUM |
| | PUMPS AND AIR COMPRESSORS, THE MUFFLER/INTAKE AND ALSO |
| | FOR THE RECEIVERS, DRYERS, AFTERCOOLERS, ETC.IF THEY |
| | ARE BEING REPLACED WITH NEW. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | 3) SHOW THE TERMINATION POINT OF THE VACUUM PUMP VENT |
| | LINE. THE DISCHARGE SHALL BE A MINIMUM OF 25 FEET FROM |
| | ANY DOOR, WINDOW, AIR INTAKE, OR OTHER OPENINGS IN |
| | BUILDINGS. NFPA 99 SEC.5.1.3.7.6.2. |
| | 4) THE MEDICAL AIR INTAKE SHALL BE LOCATED A MINIMUM OF |
| | 25 FEET FROM VENTILATING SYSTEM EXHAUSTS, PLUMBING |
| | VENTS, VACUUM DISCHARGES, OR OTHER AREAS THAT CAN |
| | COLLECT OTHER NOXIOUS FUMES. NFPA 99 SEC. 5.1.3.6.3.11. |
| | |
| | 6) SHT.P002 - DETAIL # 7 - A PRESSURE INDICATOR(S) |
| | SHALL BE LOCATED DOWNSTREAM OF EACH REGULATOR OR |
| | IMMEDIATELY DOWNSTREAM OF THE ISOLATING VALVES FOR THE |
| | REGULATORS PER NFPA 99 SEC. 5.1.3.5.5.1 (3). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |