| 2019-08-20 10:01:50 | 8/20/19 |
| | |
| | A FEW OF THE PEVIOUS FIRE COMMENTS DO NOT APPEAR TO BE |
| | ADDRESSED. |
| | |
| | |
| | |
| | 1) COMPLIED |
| | |
| | |
| | |
| | 2) PROVISO COMMENT: |
| | |
| | SHEET A 575 - THERE ARE INDICATIONS OF CARDER READERS |
| | AND ACCESS CONTROL WITHIN THE DOOR SCHEDULE. |
| | |
| | CARD READER AND ACCESS CONTROL SHALL BE INSTALLED UNDER |
| | SPEARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | ALL DEVICES AND EQUIPMENT FOR CARD READERS AND ACCESS |
| | CONTRAL SHALL FUNCTION/OPERATE UNDER THE REQUIREMENTS |
| | OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | |
| | |
| | 3) COMPLIED |
| | |
| | |
| | |
| | 4) COMPLIED |
| | |
| | |
| | 5) PROVISO COMMENT: |
| | |
| | SHEET G 410 - THERE IS AN INDICATION OF A TEMPORARY |
| | AMBULANCE CANOPY. THERE IS NO DETAIL PLAN SHEET OR |
| | CALL-OUT DRAWING. |
| | |
| | IF THIS A TENT STRUCTURE, IS THE FABRIC FIRE RETARDENT, |
| | SIZE, HEIGHT, SIDES, LIGHTING, ETC.? |
| | |
| | ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) PROVISO COMMENT: |
| | |
| | SHEET G 410 - A CONSTRUCTION BARRIER IS INDICATED. |
| | THERE IS NO DETAIL PLAN SHEET OR CALL-OUT DRAWING. |
| | |
| | WILL THIS AREA BE CONSTRUCTION MATERIAL, HAVE LIGHTING, |
| | EXIT SIGNAGE, SIDES, SPRINKLER PROTECTION, FIRE ALARM |
| | DEVICES, ETC. |
| | |
| | SHOP DRAWINGS REQUIRED |
| | |
| | |
| | |
| | 7) PROVISO COMMENT: |
| | |
| | SHEET G 410 - A TEMPORARY PUB ED CANOPY IS INDICATED. |
| | WHAT IS THE PURPOSE AND OCCUPANCY CLASSIFICATION OF |
| | THIS CANOPY? |
| | |
| | EDUCATION CLASSROOM, ASEEMBLY GATHERING AREA,? HOW WILL |
| | IT BE CONSTRUCTED? IS IT TEMPORARY TENT WITH SIDES? |
| | |
| | ANY TEMPORAY TENT STRUCTURE SHALL BE INSTALLED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS THAT INCLUDE, THE |
| | ABOVE. |
| | |
| | |