| Date |
Text |
| 2019-07-14 06:21:04 | 1) SHT. G171 - DETAILS #1,2,3 - THERE IS NO APPROVED |
| | LISTING FOR THESE PENETRATION DETAILS. CLARIFY. AN |
| | ENGINEERING JUDGEMENT MAY BE REQUIRED FROM UL. 2017 FBC |
| | SEC. 714. |
| | 2) SHT. G175 - DETAIL #6 - CLARIFY THE LOCATION OF THE |
| | REQUIRED CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN. |
| | THE CLEAR FLOOR SPACE SHALL COMPLY WITH 2107 FBC SEC. |
| | 602.2 AND BE CENTERED ON THE UNIT. |
| | 3) SHT. A600 - DETAIL #2 - SHOW THE CLEAR INSIDE |
| | DIMENSIONS (L X W) OF THE ACCESSIBLE SHOWER. TRANSFER |
| | SHOWERS SHALL BE 36 INCHES BY 36 INCHES AND SHALL |
| | COMPLY WITH 2017 FBC - ACCESSIBILITY SEC.608.2. |
| | 4) GRAB BARS IN THE TRANSFER SHOWER SHALL COMPLY WITH |
| | 2017 FBC-ACCESSIBILITY SEC. 608.3.1. |
| | 5) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN THE SHOWER |
| | AND COMPLY WITH 2017 FBC-ACCESS/ SEC.608.6. |
| | 6) THRESHOLD FOR THE SHOWER SHALL COMPLY WITH 2017 FBC |
| | -ACCESS. SEC.608.7. |
| | 7) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH |
| | 2017 FBC- ACCESS. SEC. 610.3.2. |
| | 8) SHT.A351 - DETAIL #1 - THE OVERFLOW SCUPPER SHALL BE |
| | LOCATED NO MORE THAN 4 INCHES ABOVE THE FINISHED ROOF |
| | COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO |
| | REQUIRED VERTICAL LEADERS OR DOWNSPOUTS PER 2017 FBC |
| | SEC.1503.4.2.1. |
| | 9) SHT. A600 SHOWS A GRAB BAR IN THE VERTICAL POSITION. |
| | GRAB BARS ARE NOT PERMITTED TO BE INSTALLED IN A |
| | VETICAL POSITION PER 2017 FBC-ACCESS. SEC.609.4. |
| | 10) SHT. A600 - TOILET ACCESSORY LEGEND - IDENTIFY ON |
| | THE GRAB BAR DETAILS WHICH DETAILS APPLY TO THE SIDE |
| | WALL GRAB BAR AND WHICH ONES APPLY TO THE REAR WALL. IT |
| | IS CONFUSING . 2017 FBC - ACCESS. SEC.604.5.1 & |
| | 604.5.2. |
| | 11) SHT. A600 - DETAIL # 2 - THE DOOR CANNOT SWING INTO |
| | THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY AND THE |
| | SHOWER. 2017 FBC - ACCESS. SEC.603.2.3. SEE EXCEPTION |
| | #2. |
| | 12) SHT. A652 - DETAIL #4 - SHOW THE MOUNTING HEIGHT OF |
| | THE LAVATORY IN THE NURSE'S STATION. |
| | 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE VACUUM |
| | PUMPS AND AIR COMPRESSORS, THE MUFFLER/INTAKE AND ALSO |
| | FOR THE RECEIVERS, DRYERS, AFTERCOOLERS, ETC.IF THEY |
| | ARE BEING REPLACED WITH NEW. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 14) THE VACUUM PUMPS SHALL BE PROVIDED WITH |
| | ANTIVIBRATION MOUNTINGS PERR NFPA 99 SEC.5.1.3.7.2.2. |
| | 15) SHOW THE TERMINATION POINT OF THE VACUUM PUMP VENT |
| | LINE. THE DISCHARGE SHALL BE A MINIMUM OF 25 FEET FROM |
| | ANY DOOR, WINDOW, AIR INTAKE, OR OTHER OPENINGS IN |
| | BUILDINGS. NFPA 99 SEC.5.1.3.7.6.2. |
| | 16) THE MEDICAL AIR INTAKE SHALL BE LOCATED A MINIMUM |
| | OF 25 FEET FROM VENTILATING SYSTEM EXHAUSTS, PLUMBING |
| | VENTS, VACUUM DISCHARGES, OR OTHER AREAS THAT CAN |
| | COLLECT OTHER NOXIOUS FUMES. NFPA 99 SEC. 5.1.3.6.3.11. |
| | 17) MEDICAL AIR DRYERS SHALL BE PROVIDED WITH |
| | ANTIVIBRATION MOUNTINGS PER NFPA 99 SEC. 5.1.3.6.3.7 |
| | (4). |
| | 18) SHT.P002 - DETAIL # 7 - A PRESSURE INDICATOR(S) |
| | SHALL BE LOCATED DOWNSTREAM OF EACH REGULATOR OR |
| | IMMEDIATELY DOWNSTREAM OF THE ISOLATING VALVES FOR THE |
| | REGULATORS PER NFPA 99 SEC. 5.1.3.5.5.1 (3). |
| | 19) SUBMIT RISER DIAGRAMS FOR ALL THE MEDICAL GAS |
| | PIPING TO BE INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 20) SHT. P002 - DETAIL #7 - THE PRESSURE RELIEF VALVES |
| | ON THE COMPRESSED AIR SYSTEM SHALL BE VENTED IN |
| | ACCORDANCE WITH NFPA 99 SEC. 5.1.3.5.6.1 (4). |
| | 21) IDENTIFY THE CONTINUATION POINTS OF THE MEDICAL GAS |
| | PIPING ON THE REQUESTED MEDICAL GAS RISER DIAGRAMS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 22) THE AREA(S) HOUSING THE VACUUM PUMP AND AIR |
| | COMPRESSOR SHALL BE VENTILATED PER NFPA 99 |
| | SECS.5.1.3.3.3.3, 5.1.3.6.3.1, 5.1.3.7.1.1. |
| | 23) THE NEW OUTDOOR ENCLOSURE FOR THE MEDICAL GAS SHALL |
| | BE VENTILATED PER NFPA 99 SEC.5.1.3.3.3.4 (1). |
| | 24) CLEANOUTS ARRE REQUIRED IN THE BASE OF THE |
| | STORMWATER RISERS. 2017 FBC-PLUMBING SEC.1101.8. |
| | 25) INDICATE ON THE IRRIGATION PLANS IF THERE IS AN |
| | EXISTING BACKFLOW PRVENTION DEVICE, RAIN SENSOR AND |
| | SYSTEM CONTROLLER ON THE SYSTEM. |
| | 26) SHT.P400 - THE WATER RISER DIAGRAM SHOWS WATER |
| | PIPING LINES WITH NO CONNECTION POINTS. IDENTIFY ALL |
| | CONNECTION POINTS OF THE WATER PIPING SYSTEM TO THE |
| | EXISTING SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 27) SHT. P400 - SHOW THE BACKFLOW PREVENTER ON THE THE |
| | ONE INCH WATER LINE TO THE PENTHOUSE. FBC SEC. 107.2.1. |
| | 28) SHT. P401 - THE RISER DIAGRAM INDICATES FIXTURE |
| | #503.THIS FIXTURE IS NOT LISTED IN THE PLUMBING FIXTURE |
| | SCHEDULE. CLARIFY. |
| | 29) THE SANITARY RISER SHOWS SANITARY DRAIN LINES AND |
| | VENTS WITH NO CONNECTION POINTS. IDENTIFY ALL |
| | CONNECTION POINTS OF THE SANITARY SSYSTEM TO THE |
| | EXISTING SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 30) THERE ARE NUMEROUS AREAS ON THE SANITARY RISER THAT |
| | ARE MISSING PIPE SIZES ON THE VENTS AND HORIZONTAL |
| | DRAINAGE SYSTEM. ENSURE THAT ALL AREAS OF THE SANITARY |
| | RISER ARE SIZED AND IN COMPLIANCE WITH THE PLUMBING |
| | CODE. |
| | 31) PLEASE SUBMIT AN EXPANDED SANITARY RISER DIAGRAM |
| | FOR REVIEW. THERE ARE AREAS WHERE IT IS EXTREMELY |
| | DIFFICULT TO DETERMINE IF THE DESIGN IS CODE |
| | COMPLIANT.WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |