| 2019-06-28 15:11:09 | 2 ND REVIEW: JUNE 27, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18091284 |
| | ADD: 2201 45TH ST. JFK NORTH ED ADDITION & RENOVATIONS |
| | CONT: DPR CONSTRUCTION |
| | TEL: 954-991-6200 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1) IN PROGRESS |
| | -PLEASE SEND RESIDENT INSPECTOR AGREEMENT (STARTS ON |
| | PAGE 9) VIA E-MAIL TO [email protected]. ALSO, INCLUDE |
| | RESUMES FOR ALL INSPECTORS THAT MAY BE ON-SITE. |
| | UPON APPROVAL BY CHIEF BUILDING INSPECTOR, THREE |
| | ORIGINAL COPIES WILL BE REQUESTED. |
| | |
| | 2) SHEET 088_S001 IN THE STRUCTURAL NOTES IN THE WIND |
| | DESIGN DATA THE EXPOSURE IS GIVEN AS A B EXPOSURE. IT |
| | WOULD APPEAR THAT TO THE NORTHEAST AND NORTHWEST THERE |
| | ARE C EXPOSURES SINCE MOST OF THESE AREAS HAVE LITTLE |
| | OR NO BUILDINGS, THEY ARE GRASSLANDS, OPEN LAKES, |
| | CANALS, PARKING LOTS AND HIGHWAYS. |
| | 2017 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A |
| | GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE SECTOR |
| | SHALL BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE |
| | AS DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES |
| | DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE |
| | CATEGORY AS DEFINED IN SECTION 1609.4.3. |
| | SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED |
| | OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 |
| | FEET. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, AND |
| | GRASSLANDS. |
| | -STRUCTURAL ENGINEER FEELS THAT THIS SHOULD BE EXPOSURE |
| | B. |
| | THIS HAS BEEN SENT TO THE BUILDING OFFICIAL FOR |
| | DETERMINATION. |
| | |
| | 3) PENDING BUILDING OFFICIAL DETERMINATION. |
| | |
| | 4) OK |
| | |
| | 5A) PLEASE PROVIDE THE PRODUCT APPROVAL FOR STOREFRONT |
| | SYSTEM BEING USED AT WINDOWS, OR INDICATE THAT IT WILL |
| | BE DEFERRED. |
| | |
| | 5B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | PLEASE PROVIDE PRODUCT APPROVALS THAT HAVE BEEN STAMPED |
| | FOR APPROVAL BY THE DESIGNER OF RECORD, OR PROVIDE |
| | INDEX SHEET LISTING THE PRODUCT APPROVALS AND |
| | VERIFICATION THAT WERE REVIEWED. |
| | |
| | 6) OK |
| | |
| | 7) ROOFING PRODUCT APPROVALS ? PLEASE SELECT THE SYSTEM |
| | BEING USED FROM NOA 17-1221.10 AND PROVIDE INFORMATION |
| | IF REQUIRED BY GENERAL LIMITATIONS. |
| | IF INFORMATION IS NOT KNOWN THIS CAN BECOME A DEFERRED |
| | SUBMITTAL WITH THE SUB PERMIT. |
| | |
| | 8) OK |
| | |
| | 9) OK |
| | |
| | 10) GEOTECHNICAL REPORT WAS NOT FOUND IN SUPPORTING |
| | DOCUMENTS. PLEASE UPLOAD GEOTECHNICAL REPORT, OR TELL |
| | ME WHERE IT IS LOCATED. IF IT IS COMBINED WITH ANOTHER |
| | DOCUMENT PLEASE PROVIDE AS STAND ALONE DOCUMENT. |
| | |
| | 11) ADDITIONAL PERMIT IS BEING SUBMITTED FOR TEMP |
| | WALKWAYS AND FENCING. WALKWAYS TO BE DESIGNED BY P.E. |
| | AND DIGITALLY SIGNED WITH THIRD PARTY VERIFICATION. |
| | 61G15-23 PE RULES FAC, FS 471 ENGINEERING FS. |
| | |
| | 12) OK |
| | |
| | 13) OK |
| | |
| | 14) ROOF HATCH PRODUCT APPROVAL WAS SUBMITTED |
| | PREVIOUSLY. |
| | IS THIS BEING USED, OR IS ACCESS PROVIDED BY EXTERIOR |
| | LADDER? |
| | PLEASE DELETE ROOF HATCH FROM SUPPORTING DOCUMENTS IF |
| | NOT UTILIZING. |
| | ACCESS LADDER TO BE ADDED TO PROVISO LIST TO PROVIDE |
| | LOCATION AND ATTACHMENT. |
| | |
| | 15) OK |
| | |
| | 16A) ROOFTOP EXHAUST FANS WILL BE ADDED TO DEFERRED |
| | SUBMITTAL LIST. |
| | NO RESPONSE NEEDED. |
| | |
| | 16B)-22 OK |
| | |
| | 23) PLEASE SUPPLY A SURVEY FOR THIS PROPERTY INDICATING |
| | THE DISTANCE FROM THE CURRENT BUILDING LOCATION TO THE |
| | EAST PROPERTY LINE TO VERIFY THE EXTERIOR WALL RATING |
| | FBC-B TABLE 602 AND THE AMOUNT OF ALLOWABLE OPENINGS |
| | FOR UNPROTECTED AND SPRINKLERED FBC-B TABLE 705.8. |
| | I COULD NOT FIND THE SURVEY IN DRAWINGS OR SUPPORTING |
| | DOCUMENTS. |
| | PLEASE UPLOAD THE EXISTING SURVEY. |
| | |
| | 24) OK |
| | |
| | 25) OK |
| | |
| | |
| | |
| | |
| | |