| 2019-02-26 17:48:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18091284 |
| | 2/26/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | FGI- GUIDELINES FOR DESIGN AND CONSTRUCTION OF |
| | HOSPITALS AND OUTPATIENT FACILITIES- 2014. |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M002: PROVIDE THE MINIMUM EFFICIENCY RATINGS |
| | OF THE DUCTLESS SYSTEMS AND THE CHILLERS IN THE |
| | EQUIPMENT SCHEDULES- SEE TABLES C403.2.3(1) & |
| | C403.2.3(7) FBC M. |
| | |
| | 2) M110B & M301: PROVIDE A AUTOMATICALLY CONTROLLED |
| | DAMPER FOR THE O/A INTAKE DUCT FOR AHU-22- SECTION |
| | C403.2.4.2 FBC M. |
| | |
| | 3) M110B & M301: SHOW THE LOCATION OF THE REQUIRED DUCT |
| | SMOKE DETECTOR FOR AHU-22- SECTION 606.2.1 FBC M. |
| | |
| | 4) M110B: INDICATE THE TYPE OF DUCTWORK AND DIFFUSERS |
| | TO BE INSTALLED IN THE TRAUMA ROOM- SEE TABLE 6-2 |
| | ASHRAE 170-2008 |
| | |
| | 5) M404, DETAIL 1: INDICATE HOW THE FAN CURB WILL BE |
| | ATTACHED TO THE STRUCTURE AND SUBMIT A MIAMI-DADE NOA |
| | FOR THE EXHAUST FANS PER NOTE 7- SECTION 301.15 FBC M. |
| | |
| | 6) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE CHILLER AND SUPPORT BASE- SECTION 301.15 FBC M. |
| | |
| | 7) REQUIRED SUBMITTALS TO BE APPROVED BY THE ENGINEER |
| | OF RECORD: |
| | |
| | A) EXHAUST FANS |
| | B) FILTER BANKS |
| | C) DUCTWORK |
| | D) TRAUMA ROOM DIFFUSERS |
| | E) FIRE AND FIRE/SMOKE DAMPERS |
| | G) TERMINAL REHEAT BOXES. |
| | |
| | 8) COMMISSIONING REPORT FOR THE MECHANICAL AND SERVICE |
| | WATER SYSTEMS ARE REQUIRED FOR CO- SEE SECTION C408 FBC |
| | EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |