| 2018-10-09 06:08:52 | 10/09/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A COMPREHENSIVE PLAN REVIEW HAS NOT BEEN PERFORMED |
| | AT THIS TIME; PLEASE PROVIDE INFORMATION AS REQUESTED |
| | BELOW, WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 2. PLEASE PROVIDE A PLUMBING RISER DIAGRAM FORM WATER |
| | HEATER TO COLLECTOR TACK AND SHOW THERMAL EXPANSION |
| | WITH TYPE OF INSULATION, WPB AMENDMENTS TO THE FBC SEC. |
| | 107.3.5.3 (11) RESIDENTIAL PLUMBING. |
| | 3. PLEASE PROVIDE APRICUS INSTALLATION MANUAL WHICH IS |
| | REFERRED ON NOT #5, WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. THERE ARE TWO COLLECTOR SPECIFIED ON PLANS, ETC 20 |
| | AND ETC 30, PLEASE REFLECT CORRECT ONE ON ALL AREAS, |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 5. IS THIS A TILT OR A FLUSH MOUNT UNIT, PLEASE |
| | CLARIFY, WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 6. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR THIS |
| | UNIT, WPB AMENDMENTS TO THE FBC SEC. 105.1 |
| | 7. THE ADDRESS OF PROJECT OR RESIDENCE MUST BE ON PLAN. |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |