Plan Review Notes
Plan Review Notes For Permit 18091206
Permit Number 18091206
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2018-09-28 15:57:37PERMIT # 18091206
  
 REVIEW COMMENTS - CONDITIONALLY APPROVED - COMPLY VIA
 INSPECTION ON 10/01/18
  
 1) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
 2) PROVIDE PORTABLE FIRE EXTINGUISHERS AND NOTE ON THE
 SITE PLAN WHERE THESE EXTINGUISHERS WILL BE LOCATED.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET. PROVIDE TYPE K EXTINGUISHERS WHEN
 COOKING WITH GREASE OR WHEN PRODUCING SMOKE OR
 GREASE-LADEN VAPORS.
  
 3) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES. PROVIDE DISTANCE OF TENT FROM
 NEAREST STRUCTURES.
  
 4) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
 THIS TENT IS 3,200 SQUARE FEET AND, ALTHOUGH NOT
 SPECIFICALLY MENTIONED ON DOCUMENTS PROVIDED, APPEARS
 TO BE ENCLOSED WITH SIDEWALLS. EMERGENCY LIGHTING AND
 ILLUMINATED EXIT SIGNS ARE REQUIRED.
  
 5) PLAN DOES NOT INDICATE WHERE THE DESIGNATED MEANS OF
 EGRESS IS. PLEASE NOTE THAT 2 MEANS OF EGRESS IS NEEDED
 AND SHALL BE IDENTIFIED BY AN ILLUMINATED EXIT SIGN.
 EGRESS SHALL ALSO COMPLY WITH ALL RELEVANT REQUIREMENTS
 OF NFPA 101: CHAPTER 7 (MEANS OF EGRESS).
  
 6) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 7) GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE. THIS TENT APPEARS TO HAVE A/C UNITS
 ATTACHED, HOWEVER THE POWER SOURCE FOR THESE UNITS IS
 NOT PROVIDED. PLEASE PROVIDE THESE DETAILS AND, IF
 APPLICABLE, SHOW THE LOCATION OF THE GENERATOR AND/OR
 POWER SOURCE.
  
 8) MEANS OF EGRESS ACCESS, AISLE ACCESSWAYS, AND AISLES
 SERVING SEATING AT TABLES SHALL COMPLY WITH NFPA 101:
 12.2.5. PLEASE PROVIDE A MORE DETAILED SITE PLAN THAT
 CLEARLY SHOWS THE AISLE WIDTHS AND TRAVEL DISTANCES.
  
 9) THE TENT IS 3,200 SQ FT AND FOR THIS PARTICULAR USE
 MUST COMPLY WITH THE OCCUPANT LOAD FACTORS FOR ASSEMBLY
 OCCUPANCIES, AS LISTED UNDER NFPA 101: CHAPTER 7, TABLE
 7.3.1.2. IT APPEARS THAT SEATING IS BEING PROVIDED FOR
 280 PERSONS, HOWEVER, KEEPING THE LOAD FACTORS AND
 REQUIREMENTS FOR AISLES/AISLE ACCESSWAYS, IT APPEARS
 THAT THIS MAY BE PRESENTING A SITUATION OF
 OVERCROWDING. PLEASE REVIEW AND PROVIDE THE OCCUPANT
 LOAD AND OCCUPANT LOAD LAYOUT THAT PROPERLY COMPLIES
 WITH ALL CODE REQUIREMENTS.
  
 10) PLEASE PROVIDE THE SET DATE. A FIRE INSPECTION MAY
 BE CONDUCTED AFTER SET-UP TO ENSURE COMPLIANCE WITH ALL
 RELEVANT FIRE CODES.
  
 CONDITIONALLY APPROVED - COMPLY VIA INSPECTION ON
 10/01/18
  
 BY STEVEN KENNEDY PER DISCUSSION WITH PETER LEDUC FIRE
 MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  