| 2019-01-09 17:06:01 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAKDOWN BY |
| | RECONFIGURING THE WOMENS BATHROOM ARE THERE ANY OTHER |
| | BATHROOMS IN THIS OCCUPANCY WEN I DID THE CALCULATIONS |
| | USEING THE OCCUPANT LOAD ON SHT. T0.2 I CAME UP WITH 5 |
| | MEN'S AND 7 WOMEN'S TOILETS PER FBC PL TABLE 403.1 |
| | PLEASE CLARIFY HOW YOU ARE COMPLYING WITH THE REQUIRED |
| | FIXTURE COUNT. |
| | 2. PLEASE INDICATE ON THE PLAN WHAT LEVEL OF ALTERATION |
| | THIS IS. PER FBC EXISTING CH 5 |
| | 3. PROVIDE ISOMETRIC DRAWINGS FOR THE NEW WORK AT THE |
| | SERVING STATIONS AND BISTRO BAR INCLUDING WATER AND |
| | SANITARY. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | 4. SHT. P2.01 DETAIL #3 SHOWS A TEMPERATURE OF 140 ON |
| | THE BRANCH TO THE DOUBLE LAVATORY IT SHOULD BE ONLY 110 |
| | PROVIDE THROUGH A TEMPERATURE LIMITING DEVICE COMPLING |
| | WITH ASSE 1070. PER FBC PL 416.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |