2019-01-09 17:06:011ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAKDOWN BY
 RECONFIGURING THE WOMENS BATHROOM ARE THERE ANY OTHER
 BATHROOMS IN THIS OCCUPANCY WEN I DID THE CALCULATIONS
 USEING THE OCCUPANT LOAD ON SHT. T0.2 I CAME UP WITH 5
 MEN'S AND 7 WOMEN'S TOILETS PER FBC PL TABLE 403.1
 PLEASE CLARIFY HOW YOU ARE COMPLYING WITH THE REQUIRED
 FIXTURE COUNT.
 2. PLEASE INDICATE ON THE PLAN WHAT LEVEL OF ALTERATION
 THIS IS. PER FBC EXISTING CH 5
 3. PROVIDE ISOMETRIC DRAWINGS FOR THE NEW WORK AT THE
 SERVING STATIONS AND BISTRO BAR INCLUDING WATER AND
 SANITARY. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 4. SHT. P2.01 DETAIL #3 SHOWS A TEMPERATURE OF 140 ON
 THE BRANCH TO THE DOUBLE LAVATORY IT SHOULD BE ONLY 110
 PROVIDE THROUGH A TEMPERATURE LIMITING DEVICE COMPLING
 WITH ASSE 1070. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  