| 2018-12-27 13:44:37 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18091199 |
| | REVIEWED: DECEMBER 27, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2. [FBC EXISTING 501]STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | |
| | 3. [FBC 804.2]CLASSIFICATION. INTERIOR FLOOR FINISH AND |
| | FLOOR COVERING MATERIALS REQUIRED BY SECTION 804.4.2 TO |
| | BE OF CLASS I OR II MATERIALS SHALL BE CLASSIFIED IN |
| | ACCORDANCE WITH NFPA 253. THE CLASSIFICATION REFERRED |
| | TO HEREIN CORRESPONDS TO THE CLASSIFICATIONS DETERMINED |
| | BY NFPA 253 AS FOLLOWS: CLASS I, 0.45 WATTS/CM2 OR |
| | GREATER; CLASS II, 0.22 WATTS/CM2 OR GREATER. |
| | A) STATE FLOORING FINISH CLASSIFICATION FOR NEW WORK ON |
| | SHEET T.03 SECTION 10. |
| | B) WHAT IS THE TOTAL AREA OF FLOOR WHERE WORK IS |
| | OCCURING AND WHAT IS THE AFFECTED AREA? |
| | C) WHAT IS THE EXISTING OCCUPANT LOAD OF THE WORK AREA? |
| | |
| | 4. [FBC 107.5.3]SHEET ID2.01 SHOWS DETAIL CUT 11/ID4.22 |
| | IN BAR AREA. UPDATE THE PAGE NUMBER BECAUSE IT ISN'T IN |
| | THE SET, OR REMOVE IF NOT IN USE. ALSO, SAME COMMENT |
| | FOR SHEET ID2.02 DETAIL CUT 13/ID4.22 AT SERVER 3 AND |
| | OPEN ENTRY. |
| | SHEET ID0.01 ALSO SHOWS DETAIL CALL OUTS TO SHEET |
| | ID4.22. IS THIS SHEET MISSING, OR ARE THE DETAILS ON |
| | ANOTHER SHEET. PLEASE UPDATE ACCORDINGLY. |
| | |
| | 5. [FBC 107.5.3]ENLARGED PLANS SHOW DOOR TYPE CALL |
| | OUTS, BUT I CAN'T FIND DOOR SCHEDULE. PLEASE PROVIDE |
| | DOOR SCHEDULE WITH DOOR SIZES, TYPE AND IF CLOSERS ARE |
| | PROVIDED. |
| | ALSO, ADD DOOR CALL OUT TO THE DOOR AT BISTRO BAR. |
| | |
| | 6. [FBC 1210.2.2]WALLS AND PARTITIONS. WALLS AND |
| | PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. |
| | PLEASE VERIFY TILE FINISH WALL HEIGHT TO COMPLY WITH |
| | 1210.2.2. |
| | |
| | 7. [FBC 410.4]PLATFORM CONSTRUCTION. PERMANENT |
| | PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS AS REQUIRED |
| | FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN WHICH |
| | THE PERMANENT PLATFORM IS LOCATED. PERMANENT PLATFORMS |
| | ARE PERMITTED TO BE CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD FOR TYPES I, II AND IV |
| | CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN |
| | ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN |
| | 3,000 SQUARE FEET (279 M2) IN AREA. |
| | PLEASE ADD NOTE TO SHEET ID4.02 DETAIL 9 THAT THE WOOD |
| | USED TO BUILD PLATFORM IS TO BE CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD. |
| | |
| | 8. [FBC A505.10.1]TOP AND BOTTOM EXTENSION AT |
| | RAMPS.RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE |
| | THE LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE |
| | TOP AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO |
| | A WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE |
| | CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN. |
| | PLEASE REVIEW RAMP TO PLATFORM 117 FOR COMPLIANCE WITH |
| | 505.10.1 IN ACCESSIBILITY CODE. |
| | |
| | 9. [FBC A226.1]THE ACCESSIBILITY CODE REQUIRES 0.05 % |
| | OF ALL SEATING TO BE ACCESSIBLE. |
| | WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION |
| | OF FOOD OR DRINK, AT LEAST 0.05 PERCENT OF THE SEATING |
| | SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL |
| | COMPLY WITH 902. |
| | SHOW HOW BISTRO BAR WILL COMPLY WITH 226.1 AND 902. |
| | |
| | 10. [FBC 1016.2]EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS THROUGH |
| | INTERVENING SPACES SHALL COMPLY WITH THIS SECTION. |
| | WHEN EXITING MULTI PURPOSE ROOM THROUGH EXIT 116 OR |
| | ENTRY 115, DO THEY LEAD TO THE OUTSIDE? |
| | IF THEY GO THROUGH INTERVENING SPACES INCLUDE THE |
| | TRAVEL DISTANCE ON LIFE SAFETY AND REVIEW FOR |
| | COMPLIANCE WITH 1016.2. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |