2018-10-19 14:08:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS PERMITTED UNDER THE FBC FIFTH
 EDITION (2014). PLEASE REVISE THE CONSTRUCTION
 DOCUMENTS ACCORDINGLY.
  
 2) THIS PROJECT IS LOCATED IN EXPOSURE C AND THE PLANS
 AND OTHER CONSTRUCTION DOCUMENTS THAT WERE SUBMITTED
 ARE FOR EXPOSURE B. PLEASE REVISE THE CONSTRUCTION
 DOCUMENTS ACCORDINGLY. FBC 1609.4.3 NOTE: THIS
 STRUCTURE CAN BE CLASSIFIED AS A RISK CATEGORY I,
 RATHER THAN A RISK CATEGORY II WHICH WOULD LOWER THE
 WIND SPEED.
  
 3) THE CALCULATIONS FOR THE + 110' -11" TALL POLE
 REQUIRES A MINIMUM DEPTH OF 28'-6" AND THE POLE
 ELEVATIONS ON SHEET S4.1 HAS 28'. PLEASE CLARIFY. FBC
 107.2.1
  
 4) PROVIDE A DETAIL OF THE POLE FOUNDATION ON THE
 DRAWINGS. SPECIFY THE REQUIRED DEPTH OF THE CONCRETE
 THAT WILL UNDERNEATH THE POLES. SPECIFY THE MINIMUM
 THICKNESS OF THE CONCRETE THAT WILL ENCASE THE POLES ON
 THE SIDES. SPECIFY THE REQUIRED COMPRESSION STRENGTH OF
 THE CONCRETE. FBC 107.2.1.2
  
 5) SPECIFY THE LOCATION OF THE PROJECT ON THE NETTING
 POLES & FOUNDATION CALCULATIONS. "TOP GOLF" IS THE NAME
 OF THE PROJECT THAT IS LISTED ON THE CALCULATIONS AND
 THIS PROJECT IS "DRIVE SHACK". PLEASE CORRECT. FBC
 107.2.1
  
 6) PROVIDE THE NAME OF THE COMPANY AND THE SPECIAL
 INSPECTORS THAT WILL BE PERFORMING THE TESTS AND
 SPECIAL INSPECTIONS REQUIRED FOR THIS PROJECT. FBC
 110.3.9
  
  
  
  
  