| 2018-10-19 14:08:15 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THIS PROJECT IS PERMITTED UNDER THE FBC FIFTH |
| | EDITION (2014). PLEASE REVISE THE CONSTRUCTION |
| | DOCUMENTS ACCORDINGLY. |
| | |
| | 2) THIS PROJECT IS LOCATED IN EXPOSURE C AND THE PLANS |
| | AND OTHER CONSTRUCTION DOCUMENTS THAT WERE SUBMITTED |
| | ARE FOR EXPOSURE B. PLEASE REVISE THE CONSTRUCTION |
| | DOCUMENTS ACCORDINGLY. FBC 1609.4.3 NOTE: THIS |
| | STRUCTURE CAN BE CLASSIFIED AS A RISK CATEGORY I, |
| | RATHER THAN A RISK CATEGORY II WHICH WOULD LOWER THE |
| | WIND SPEED. |
| | |
| | 3) THE CALCULATIONS FOR THE + 110' -11" TALL POLE |
| | REQUIRES A MINIMUM DEPTH OF 28'-6" AND THE POLE |
| | ELEVATIONS ON SHEET S4.1 HAS 28'. PLEASE CLARIFY. FBC |
| | 107.2.1 |
| | |
| | 4) PROVIDE A DETAIL OF THE POLE FOUNDATION ON THE |
| | DRAWINGS. SPECIFY THE REQUIRED DEPTH OF THE CONCRETE |
| | THAT WILL UNDERNEATH THE POLES. SPECIFY THE MINIMUM |
| | THICKNESS OF THE CONCRETE THAT WILL ENCASE THE POLES ON |
| | THE SIDES. SPECIFY THE REQUIRED COMPRESSION STRENGTH OF |
| | THE CONCRETE. FBC 107.2.1.2 |
| | |
| | 5) SPECIFY THE LOCATION OF THE PROJECT ON THE NETTING |
| | POLES & FOUNDATION CALCULATIONS. "TOP GOLF" IS THE NAME |
| | OF THE PROJECT THAT IS LISTED ON THE CALCULATIONS AND |
| | THIS PROJECT IS "DRIVE SHACK". PLEASE CORRECT. FBC |
| | 107.2.1 |
| | |
| | 6) PROVIDE THE NAME OF THE COMPANY AND THE SPECIAL |
| | INSPECTORS THAT WILL BE PERFORMING THE TESTS AND |
| | SPECIAL INSPECTIONS REQUIRED FOR THIS PROJECT. FBC |
| | 110.3.9 |
| | |
| | |
| | |
| | |
| | |