| 2018-10-25 14:34:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3404.2 |
| | |
| | 2.PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 3.A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE E3607.3 |
| | 4.FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN |
| | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE |
| | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| | 5.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| | CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1. |
| | 6.THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER |
| | SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS |
| | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC |
| | 210.52(C)(1); FBC RE E3901.4 |
| | 7.PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D); |
| | FBC RE E3902.10 |
| | 8.GEC TOO SMALL 250.66 |
| | 9.OCP TO COTTAGE TOO LARGE |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |
| | SINCERELY, |
| | |
| | PHIL PETTY |
| | ELECTRICAL PLANS EXAMINER CHIEF ELECTRICAL INSPECTOR |
| | 561-805-6742 |
| | [email protected] |
| | |