| 2018-11-19 08:11:29 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18091195 |
| | REVIEWED: NOVEMBER 16, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE |
| | DRAINAGE PLAN. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | 2. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP |
| | CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| | AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND |
| | ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION |
| | CONTROL |
| | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| | /FORMS,-PERMITS-APPLICATIONS |
| | |
| | 3. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES |
| | REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH |
| | THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD |
| | INDEX AND SMOKE DEVELOPED INDEX. |
| | [FBC R302.10]SHEET A-21 STATES R-19 SPRAY INSULATION |
| | AND POINTS TO A FURRED CEILING. PROVIDE DETAIL OF HOW |
| | THE REQUIRED AMOUNT OF INSULATION WILL FIT WITHIN THE |
| | THERMAL ENVELOPE. |
| | |
| | 4. [FBC ENERGY 103.1.1.2]CODE COMPLIANCE CERTIFICATION. |
| | THE BUILDING?S OWNER, THE OWNER?S ARCHITECT OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | -PLEASE HAVE OWNER OR OWNERS AGENT SIGN THE ENERGY |
| | CALCULATION IN ADDITION TO THE PREPARER WHO SIGNED. |
| | |
| | PROVISOS: |
| | -PRE-FAB ALUMINUM TRELLIS, STAIRS AND GUARD RAIL |
| | ENGINEERING WILL BE A DEFFERED SUBMITTAL AS STATED ON |
| | SHEET A-1. |
| | -WINDOWS AND DOORS WILL BE A DEFFERED SUBMITTAL AS |
| | STATED ON SHEET A-1. |
| | -TRUSS SHOP DRAWINGS TO THE BUILDING INSPECTOR PRIOR TO |
| | INSTALLATION. |
| | -PROVIDE PRODUCT APPROVALS FOR ROOFING WITH SUB-PERMIT |
| | APPLICATION. |
| | -SEPARATE PERMIT WILL BE NEEDED FOR |
| | DRIVEWAY(ENGINEERING DEPT.), POOL AND FENCING. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |