| Notes |
| Date |
Text |
| 2018-10-06 13:08:30 | ****CORRECTIONS**** | | | REVISED 10/11 | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. DELEGATED ENGINEERING IS TO BE REVIEWED BY | | | STRUCTURAL ENGINEER OF RECORD, FAC61G15-23. | | | | | | 2. PRECAST CALCS SHOW A DESIGN OF 170MPH, SEE COMMENT | | | #4 AND CORRELATE IF NECESSARY. | | | | | | 3. PRECAST SHORING IS NOT DIGITALLY SIGNED. AS THE | | | ENGINEER HAS A DIGITAL SIGNATURE, PLEASE SEND THE | | | ORIGINAL TO ME VIA EMAIL (NO MARKUPS AFTER SIGNING AS | | | THAT WILL INVALIDATE THE SEAL). | | | | | | 4. GS001, WIND DESIGN CRITERIA IS IMPORTANCE FACTOR | | | III, 170MPH; SHOULDN'T THIS BE 180MPH? SEE FBC B 1609, | | | ALSO THE FOLLOWING WEBSITE: | | | | | | HTTP://WINDSPEED.ATCOUNCIL.ORG/ | | | | | | 170MPH IS OK FOR IMPORTANCE FACTOR II. EITHER REVISE | | | WIND SPEED OR IMPORTANCE FACTOR TO CORRELATE, MAKE SURE | | | THAT PRECAST MATCHES. | | | | | | 5. NA | | | | | | 6. FS553, PROVIDE PRIVATE PROVIDER STAMP AND AFFIDAVIT. | | | | | | | | | | | | | | | | | | | | | |
|