| 2018-11-07 16:00:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. A1.00, FBC 107, I WAS UNABLE TO LOCATE THE NEW |
| | FLAGPOLE OR ASSOCIATED FLAGPOLE ENGINEERING AND DETAIL. |
| | EITHER REMOVE THE REFERENCE FROM THE NARRATIVE AND |
| | CONFIRM THAT THIS IS NOT INSTALLED, OR REVISE SITE PLAN |
| | AND REVISION DESCRIPTION TO INCLUDE. UPON REQUEST THE |
| | FLAGPOLE CAN BE ADDED TO THE SCOPE OF ONE OF THE |
| | PERMITS (SHOULD BE THE BUILDING IT IS CLOSEST TO), |
| | ENGINEERING TO BE SUBMITTED AS A SUBMITTAL. THIS IS |
| | TYPICALLY REQUIRED TO BE A SEPARATE PERMIT BUT I HAVE |
| | NO OBJECTION TO THIS BEING INCLUDED IN THE SCOPE OF THE |
| | BUILDING PERMIT IF ZONING HAS NO OBJECTION. |
| | |
| | 2. A1.03, FBC B 1009.7.4, STAIR RISER IS TO BE 7? MAX |
| | UNLESS ONE OF THE EXCEPTIONS IS APPLICABLE. REVISE PLAN |
| | TO INCLUDE EXCEPTION. THE NOTE STATES THAT THIS |
| | CONDITION OCCURS AT BUILDINGS III & IV. AS THESE |
| | BUILDINGS ARE 6 UNITS (16070880, 16071058) R2, |
| | EXCEPTION 5 DOES NOT APPEAR APPLICABLE AS THE STAIR IS |
| | LOCATED OUTSIDE; IS THIS CORRECT? SEE ALSO FBC A 504.2 |
| | IF THIS PROJECT IS SUBJECT TO ACCESSIBILITY. IT APPEARS |
| | THAT THE STAIRS DO NOT SERVE ACCESSIBLE UNITS; PLEASE |
| | CONFIRM. |
| | |
| | 3. THERE ARE A NUMBER OF REFERENCES TO THE ?ADA |
| | CONSULTANT? IN THE NARRATIVE. PLEASE ADVISE; IS THIS |
| | PROJECT SUBJECT TO ADA/ FBC 2014 ACCESSIBIITY DUE TO |
| | FEDERAL FUNDS RATHER THAN GOVERNED BY FBC 2014 |
| | ACCESSIBILITY, FAIR HOUSING? IF NOT, PLEASE STATE THIS |
| | IN THE RESPONSE LETTER. NOTE THAT SOME UNITS ARE SHOWN |
| | AS FULLY ADA COMPLIANT. |
| | |
| | SEE FBC A 233.2 RESIDENTIAL DWELLING UNITS PROVIDED BY |
| | ENTITIES SUBJECT TO HUD SECTION 504 REGULATIONS. |
| | WHERE FACILITIES WITH RESIDENTIAL DWELLING UNITS ARE |
| | PROVIDED BY ENTITIES SUBJECT TO REGULATIONS ISSUED BY |
| | THE DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT (HUD) |
| | UNDER SECTION 504 OF THE REHABILITATION ACT OF 1973, AS |
| | AMENDED, SUCH ENTITIES SHALL PROVIDE RESIDENTIAL |
| | DWELLING UNITS WITH MOBILITY FEATURES COMPLYING WITH |
| | 809.2 THROUGH 809.4 IN A NUMBER REQUIRED BY THE |
| | APPLICABLE HUD REGULATIONS. RESIDENTIAL DWELLING UNITS |
| | REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH |
| | 809.2 THROUGH 809.4 SHALL BE ON AN ACCESSIBLE ROUTE AS |
| | REQUIRED BY 206. IN ADDITION, SUCH ENTITIES SHALL |
| | PROVIDE RESIDENTIAL DWELLING UNITS WITH COMMUNICATION |
| | FEATURES COMPLYING WITH 809.5 IN A NUMBER REQUIRED BY |
| | THE APPLICABLE HUD REGULATIONS. ENTITIES SUBJECT TO |
| | 233.2 SHALL NOT BE REQUIRED TO COMPLY WITH 233.3. |
| | |
| | 4. A2.05, FBC 107, SCOPE AND NATURE OF WALL CHANGES ARE |
| | NOT CLEAR. THERE IS A SECTION MARKER C A4.01; IT |
| | APPEARS THAT REVISING THIS MAY CLARIFY WALL CHANGE, OR |
| | ADD NOTES ON THE PLAN. GRAPHICS AT THE WALL CHANGED BUT |
| | I WAS UNABLE TO LOCATE LANGUAGE THAT DESCRIBED THE |
| | CHANGE. NO WALL TAGS WERE REVISED. |
| | |
| | 5. A4.03, A4.04, FBC 107, NARRATIVE STATES ?UPDATE NOT |
| | TO COMPLY WITH P-531 REQUIREMENTS?; PLEASE CLARIFY. IS |
| | P531 A REQUIRED FIRE RATED ASSEMBLY? SHOULD NARRATIVE |
| | STATE THAT THE UPDATE IS TO COMPLY? |
| | |
| | 6. A5.04, 5.08, 5.09, 5.10, CLARIFY CHANGES, NOT IN |
| | NARRATIVE. FOR EXAMPLE, SEE A5.10. A DELTA 19 |
| | COORDINATION IS NOTED BUT NOTHING CLOUDED AS REVISION |
| | 19. |
| | |
| | 7. A6.04 NARRATIVE STATES CHANGES ARE ADA RELATED, |
| | UNABLE TO LOCATE THE CHANGES (CHANGE APPEARS TO BE |
| | EXHAUST DUCT COORDINATION). EITHER REVISE PLAN TO |
| | INCLUDE CLOUDS SHOWING ADA CHANAGES OR REVISE |
| | NARRATIVE. |
| | |
| | |
| | |