Plan Review Notes
Plan Review Notes For Permit 18091122
Permit Number 18091122
Review Stop P
Sequence Number 3
Notes
Date Text
2019-04-18 15:04:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: A-6 PLUMBING PLAN; UNIT #1 & #2 SANITARY RISER.
 A. GROUND FLOOR; KITCHEN SINK SHALL DISCHARGE TO
 HORIZONTAL BRANCH DOWNSTREAM OF BATHROOM GROUP PER FBC
 PL 912.1 AND SHALL BE VENTED PER FBC PL 910.1.
 B. 2ND FLOOR; NEW CLOTHES WASHER SHALL CONNECT TO
 VERTICAL STACK BELOW THE SHOWER FIXTURE DRAIN
 CONNECTION PER FBC PL 912.1.1 AND SHALL BE VENTED PER
 FBC PL 910.1.
 C. 2ND FLOOR; KITCHEN SINK AND DISPOSAL SHALL CONNECT
 TO VERTICAL STACK BELOW THE BATHROOM FIXTURE DRAIN
 CONNECTIONS PER FBC PL 912.1.1 AND SHALL BE VENTED PER
 FBC PL 910.1. WATER CLOSET AND BATHTUB FIXTURE DRAINS
 SHALL CONNECT INDEPENDENTLY TO THE VERTICAL WET VENT.
 THE BATHTUB FIXTURE DRAIN SHALL CONNECT ABOVE OR AT THE
 SAME ELEVATION AS THE WATER CLOSET FIXTURE DRAIN. THE
 DRY-VENT CONNECTION TO THE VERTICAL WET VENT SHALL BE
 AN INDIVIDUAL OR COMMON VENT SERVING ONE OR TWO
 FIXTURES.
 2.WPB FBC 107.3.5.1.3 REQUIRES A CODE COMPLIANT WATER
 RISER DIAGRAM.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 18091122 230 ARGYLE RD
  
 NOTE: EXISTING GAS TANKLESS WATER HEATER INSTALLED
 UNDER PERMIT #16060022
  
  