| 2019-04-18 15:04:49 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL |
| | MANUAL |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 3RD REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. RE: A-6 PLUMBING PLAN; UNIT #1 & #2 SANITARY RISER. |
| | A. GROUND FLOOR; KITCHEN SINK SHALL DISCHARGE TO |
| | HORIZONTAL BRANCH DOWNSTREAM OF BATHROOM GROUP PER FBC |
| | PL 912.1 AND SHALL BE VENTED PER FBC PL 910.1. |
| | B. 2ND FLOOR; NEW CLOTHES WASHER SHALL CONNECT TO |
| | VERTICAL STACK BELOW THE SHOWER FIXTURE DRAIN |
| | CONNECTION PER FBC PL 912.1.1 AND SHALL BE VENTED PER |
| | FBC PL 910.1. |
| | C. 2ND FLOOR; KITCHEN SINK AND DISPOSAL SHALL CONNECT |
| | TO VERTICAL STACK BELOW THE BATHROOM FIXTURE DRAIN |
| | CONNECTIONS PER FBC PL 912.1.1 AND SHALL BE VENTED PER |
| | FBC PL 910.1. WATER CLOSET AND BATHTUB FIXTURE DRAINS |
| | SHALL CONNECT INDEPENDENTLY TO THE VERTICAL WET VENT. |
| | THE BATHTUB FIXTURE DRAIN SHALL CONNECT ABOVE OR AT THE |
| | SAME ELEVATION AS THE WATER CLOSET FIXTURE DRAIN. THE |
| | DRY-VENT CONNECTION TO THE VERTICAL WET VENT SHALL BE |
| | AN INDIVIDUAL OR COMMON VENT SERVING ONE OR TWO |
| | FIXTURES. |
| | 2.WPB FBC 107.3.5.1.3 REQUIRES A CODE COMPLIANT WATER |
| | RISER DIAGRAM. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 18091122 230 ARGYLE RD |
| | |
| | NOTE: EXISTING GAS TANKLESS WATER HEATER INSTALLED |
| | UNDER PERMIT #16060022 |
| | |
| | |