| 2019-04-29 15:03:47 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18091122 |
| | 4/29/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) M1: THE 14 SEER 2-TON AC SYSTEMS DON'T MATCH WITH |
| | THE ENERGY CALCULATIONS WHICH INDICATE THE SYSTEMS |
| | ARE16 SEER. THE SCHEDULE ALSO DOES NOT PROVIDE A SEER |
| | FOR THE MINI SPLIT WHICH IS LISTED AS 18 SEER IN THE |
| | ENERGY CALCS. |
| | |
| | 2) M1 & A4: THE LOUVERD AC CLOSET DOORS SHALL BE OF |
| | NON-COMBUSTIBLE CONSTUCTION MATERIALS PER SECTION 602.1 |
| | FBC M. THE DOOR SCHEDULE IS INDICATING WOOD. |
| | |
| | 3) THE 1ST REVIEW COMMENTS #3, 5, 7, 8 PRINTED BELOW |
| | STILL EXIST- PLEASE COMPLY. |
| | |
| | 3) M1: INDICATE HOW THE APARTMENTS ARE TO BE |
| | VENTILATED- NATURALLY OR MECHANICALLY -AND PROVIDE |
| | CALCULATIONS- SEE SECTIONS 401.2, 402.1, AND 403.1 FBC |
| | M. (REFER TO SECTION 403.3.2 FBC M FOR ADDITIONAL |
| | REQUIREMENTS). |
| | . |
| | 5) M1: SHOW HOW LOCAL EXHAUST SYSTEMS ARE BEING |
| | PROVIDED FOR THE BATH AND KITCHEN- SECTION 403.3.2.3 |
| | FBC M. |
| | |
| | 7) M2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | VENTLESS DRYER, AND THE COOKING APPLIANCES- SECTIONS |
| | 304.1 AND 504.1 FBC M. |
| | |
| | 8) M2: CLARIFY IF NEW EXHAUST HOODS FOR THE COOKING |
| | APPLIANCES ARE TO BE INSTALLED AND PROVIDE DETAILS AND |
| | SPECIFICATIONS- SECTION 505.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |