| 2019-02-20 11:30:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18091122 |
| | 2/20/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS IN ACCORDANCE WITH SECTION R403.7.1 FBC EC. |
| | |
| | 2) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATION |
| | IN ACCORDANCE WITH SECTION 202 FBC EC. SUBMIT AN ENERGY |
| | COMPLIANCE REPORT AS REQUIRED BY SECTION R505.1.1, AND |
| | R101.5.1.1 FBC EC |
| | |
| | 3) INDICATE HOW THE APARTMENTS ARE TO BE VENTILATED- |
| | NATURALLY OR MECHANICALLY -AND PROVIDE CALCULATIONS- |
| | SEE SECTIONS 401.2, 402.1, AND 403.1 FBC M. |
| | |
| | 4) THE MODEL NUMBERS ON THE SUBMITTED CUT SHEET FOR THE |
| | MINI-SPLIT SYSTEM DO NOT MATCH THE MODEL NUMBERS ON |
| | SHEET M1. |
| | |
| | 5) M-1: SHOW HOW LOCAL EXHAUST SYSTEMS ARE BEING |
| | PROVIDED FOR THE BATH AND KITCHEN- SECTION 403.3.2.3 |
| | FBC M. |
| | |
| | 6) M-1: INDICATE WHAT APPLIANCE IS LOCATED IN THE |
| | CLOSET BY THE STAIRS. |
| | |
| | 7) M-2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | VENTLESS DRYER, AND THE COOKING APPLIANCES- SECTIONS |
| | 304.1 AND 504.1 FBC M. |
| | |
| | 8) M-2: CLARIFY IF NEW EXHAUST HOODS FOR THE COOKING |
| | APPLIANCES ARE TO BE INSTALLED AND PROVIDE DETAILS AND |
| | SPECIFICATIONS- SECTION 505.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |