Plan Review Notes
Plan Review Notes For Permit 18091119
Permit Number 18091119
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-09-28 12:06:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE SPACE BETWEEN THE NEW HOSTESS STAND AND THE NEW
 BOOTH DOES NOT HAVE ADIMENSION INDICATED. THIS AREA IS
 AN EGRESS TRAVEL PATH.
  
 THIS DIMENSION SHALL NOT BE LESS THAN 36" PER NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 7.3.4 MINIMUM WIDTH.
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE
 PROVIDED IN 7.3.4.1.1 THROUGH 7.3.4.1.3, SHALL BE AS
 FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN
 THIS CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS
 CHAPTER AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY A
 MINIMUM WIDTH
  
  
  
 2) THERE IS AN INCORRECT REFERENCE TO THE CURRENT
 FLORIDA FIRE PREVENTION CODE; 2014 5TH EDITION.
  
 THE PROPOSED PROJECT SHALL COMPLY WITH CURRENT FFPC ;
 2017, 6TH EDITION.
  
 PLEASE ENSURE COMPLAINCE AND UPDATE YOUR REFERENCES
 ACCORDINGLY.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  