| 2018-11-05 10:55:51 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18091119 |
| | ADD: 851 VILLAGE BLVD. SUITE: 602A |
| | CONT: MASTER PLAN INC. |
| | TEL: 561-683-9972 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 5/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE SUBMIT AN ORIGINAL PERMIT APPLICATION BEFORE |
| | THE PERMIT CAN BE ISSUED. |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION SECTION 105.1 REQUIRED SIGNATURES, |
| | ORIGINAL SIGNATURE NOT COPIES. |
| | 2) SHEET A-1: |
| | 2A) HEADING APPLICABLE CODES AND STANDARDS INDICATES |
| | THE SUBMITTED PLANS WERE DESIGNED UNDER THE 2014 5TH |
| | EDITION OF THE FLORIDA FAMILY OF CODES. PLEASE UPDATE |
| | THE PLANS, DEC. 31/ 2017 STATEWIDE THE 2017 6TH EDITION |
| | OF THE FLORIDA FAMILY OF CODES WAS ADOPTED STATEWIDE. |
| | 2B) UNDER THE HEADING BUILDING BASICS THE OCCUPANCY |
| | CLASSIFICATION IS A A-2 SMALL ASSEMBLY. PLEASE SEE 2017 |
| | FBC-B SECTION 303.1.2 FOR SMALL ASSEMBLY, THE SMALL |
| | ASSEMBLY HAS TO BE AN ACCESSORY OCCUPANCY TO THE MAIN |
| | OCCUPANCY TYPE, AND A ROOM OR SPACE LESS THAN 750 SQ. |
| | FT. AND AN OCCUPANT LOAD OF LESS THAN 50. THIS TENANT |
| | SPACE IS AN A-2 OCCUPANCY RESTAURANT WITH A DECLARED |
| | OCCUPANT LOAD OF 92 OCCUPANTS, PLEASE UPDATE PLANS. |
| | 3C) UNDER THE HEADING BUILDING BASICS THE MINIMUM |
| | BUILDING TYPE IS LABELED A TYPE III CONSTRUCTION. |
| | PLEASE IDENTIFY THE BUILDING TYPE AS EITHER TYPE IIIA |
| | OR IIIB? SEE 2017 FBC-B 504.4 & TABLE 506.2. |
| | 3D) THE PLANS DOES NOT INDICATE IF THE BUILDING IS FIRE |
| | SPRINKLERED OR NOT, COMPLIANCE WITH 2017 FBC-B TABLE |
| | 508.4 REQUIRING 1 OR 2 HOUR FIRE SEPARATION FROM OTHER |
| | OCCUPANCIES WALL TYPES AND RATINGS CANNOT BE |
| | DETERMINED? |
| | 3E) THE COVERSHEET INDICATES THERE IS 84 SEATS FOR THIS |
| | ASSEMBLY OCCUPANCY, 84X0.05%= 4.2 OR 5 REQUIRED |
| | ACCESSIBLE SEATS ARE REQUIRED TO BE SHOWN ON THE PLANS |
| | TO SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 226.1 WHERE DINING SURFACES ARE PROVIDED FOR |
| | THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF |
| | THE SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 3E)(1) 226.2 DISPERSION. DINING SURFACES AND WORK |
| | SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 3E)(2) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 3F) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING |
| | PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 3F)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 3F)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3G) THE P. O. S. (POINT OF SALE) DOES NOT PROVIDE ANY |
| | ELEVATION VIEW OR CUT SECTION THROUGH THIS ELEMENT |
| | SHOWING COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE |
| | SECTION CHECK WRITING SURFACES. 2017 ACCESS. CODE |
| | 904.3.3 CHECK WRITING SURFACES. |
| | ? WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| | WITH 902.3. 902.3HEIGHT. |
| | THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND |
| | SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. |
| | THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND |
| | THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. |
| | |
| | 4) ZONING HOLD ON PERMIT, NEW ROOF TOP MECHANICAL |
| | EQUIPMENT MUST BE SCREENED. SHOW COMPLIANCE WITH |
| | 2017 FBC-B 1509.6 MECHANICAL EQUIPMENT SCREENS. |
| | MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF |
| | THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN |
| | ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER |
| | THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS |
| | SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| | FIRE-RESISTANCE RATING REQUIREMENTS. |
| | |
| | 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT |
| | SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT |
| | ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT |
| | ON THE MECHANICAL EQUIPMENT SCREEN. EXCEPTION: WHERE |
| | LOCATED ON BUILDINGS OF TYPE IA CONSTRUCTION, THE |
| | HEIGHT OF MECHANICAL EQUIPMENT SCREENS SHALL NOT BE |
| | LIMITED. |
| | |
| | 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| | ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES HIGH OR WALKING ON ROOFS HAVING |
| | A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (33-PERCENT SLOPE). |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |