| 2019-02-12 05:09:10 | 1) THE TDH CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM | | | COMPONENTS INCLUDING FITTINGS, VALVES, AND CHLORINATOR. | | | ALL SYSTEM COMPONENTS EXCEPT THE PUMP. THE TDH | | | CALCULATIONS DO NOT APPEAR TO HAVE INCCLUDED THESE | | | COMPONENTS. THE PIPE AND FITTINGS FOR THE TANNING LEDGE | | | MUST ALSO BE INCLUDED IN THE TDH CALCULATIONS.THE | | | SIMPLIFIED METHOD IS NO LONGER PERMITTED TO BE USED. | | | CLARIFY.2ND REQUEST.ANSI/APSP/ICC 7-2013 | | | SECS.4.4.9,4.4.9.1. | | | 2) SUBMIT TWO LEGIBLE COPIES OF THE CLEAR COMFORT | | | SANITATION. | | | 3) THE POOL PLANS DRAWN BY THE POOL CONTRACTOR SHALL BE | | | SIGNED AND SEALED BY AN ENGINEER PER FBC 107.1. | | | 4) THE PLANS DRAWN BY THE POOL CONTRACTOR SHOW RETURN | | | LINES FOR THE TANNING LEDGE BUT WHERE IS THE MAIN | | | DRAIN/ SUCTION LINE FOR FILTERING THE WATER? | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|