2018-11-16 14:01:051) PAGE 7 OF THE LATHAM POOL PRODUCT DRAWINGS REFERS TO
 THE 2007 FLORIDA BUILDING CODE. THE CODE IN EFFECT IS
 THE 2017 EDIRION AND THE SECTION REFERENCED ON THE PLN
 ( SEC. 424) IS WRONG.
 2) REMOVE ALL OLD AND MULTIPLE COPIES OF DOCUMENTS FROM
 THE PERMIT PACKAGE AND COMPILE THE DOCUMENTS INTO TWO
 COMPLETE SETS OF PLANS FOR REVIEW. WPB AMEND. TO FBC
 SEC. 107.1.
 3) SUBMIT TWO COPIES OF LEGIBLE SPECIFICATIONS FOR THE
 CLEAR COMFORT SANITATION SYSTEM FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
 4) THERE ARE TWO DIFFERENT POOL SPECS IN THE PERMIT
 PACKAGE THAT SHOW TWO DIFFERENT PUMPS TO BE INSTALLED.
 CLARIFY.
 5) THE TOTAL DYNAMIC HEAD CALCULATIONS DO NOT SHOW THE
 FRICTION LOSS FOR ALL THE SUCTION AND RETURN FITTINGS
 OR VALVES. SUBMIT NEW CALCULATIONS INCORPORATING THE
 FRICTION LOSS FOR THE VALVES AND FITTINGS. APSP 7-2013
 SEC.4.4.9, 4.4.9.1.
 6) IDENTIFY ON THE PUMP CURVE THAT IS ON THE TDH
 CALCULATION SHEET WHICH CURVE KEY APPLIES TO THIS
 INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW