| Plan Review Notes For Permit 18091117 |
| Permit Number |
18091117 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-11-16 14:01:05 | 1) PAGE 7 OF THE LATHAM POOL PRODUCT DRAWINGS REFERS TO | | | THE 2007 FLORIDA BUILDING CODE. THE CODE IN EFFECT IS | | | THE 2017 EDIRION AND THE SECTION REFERENCED ON THE PLN | | | ( SEC. 424) IS WRONG. | | | 2) REMOVE ALL OLD AND MULTIPLE COPIES OF DOCUMENTS FROM | | | THE PERMIT PACKAGE AND COMPILE THE DOCUMENTS INTO TWO | | | COMPLETE SETS OF PLANS FOR REVIEW. WPB AMEND. TO FBC | | | SEC. 107.1. | | | 3) SUBMIT TWO COPIES OF LEGIBLE SPECIFICATIONS FOR THE | | | CLEAR COMFORT SANITATION SYSTEM FOR REVIEW. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 4) THERE ARE TWO DIFFERENT POOL SPECS IN THE PERMIT | | | PACKAGE THAT SHOW TWO DIFFERENT PUMPS TO BE INSTALLED. | | | CLARIFY. | | | 5) THE TOTAL DYNAMIC HEAD CALCULATIONS DO NOT SHOW THE | | | FRICTION LOSS FOR ALL THE SUCTION AND RETURN FITTINGS | | | OR VALVES. SUBMIT NEW CALCULATIONS INCORPORATING THE | | | FRICTION LOSS FOR THE VALVES AND FITTINGS. APSP 7-2013 | | | SEC.4.4.9, 4.4.9.1. | | | 6) IDENTIFY ON THE PUMP CURVE THAT IS ON THE TDH | | | CALCULATION SHEET WHICH CURVE KEY APPLIES TO THIS | | | INSTALLATION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|