| Plan Review Notes For Permit 18091101 |
| Permit Number |
18091101 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-14 09:52:03 | 1) THERE ARE THREE DIFFERENT GAS DRAWINGS IN THIS | | | PERMIT SUBMITTAL PACKAGE. REMOVE ALL OLD DOCUMENTS FROM | | | THIS SUBMITTAL AND ORGANIZE THE DOCUMENTS INTO TWO | | | COMPLETE SETS OF PLANS FOR REVIEW.FBC SEC. 107.2.1. | | | 2) SIZE THE EXISTING GAS LINE TO THE INTERIOR OF THE | | | HOUSE AND SIZE THE EXISTING LINE TO THE POOL HEATER. | | | 3) SHOW THE DISTANCE FROM THE MEDIUM PRESSURE | | | REGULATORS TO THE FURTHEST OUTLET ON THE LOW PRESSURE | | | SIDE OF THE SYSTEM. I HAVE INCLUDED A COPY OF THE | | | EXISTING GAS DRAWING IN THE PERMIT SUBMITTAL PACKAGE | | | FOR REFERENCE. | | | 4) SHOW THE BTU LOAD OF THE EXISTING BBQ ON THE PLANS. | | | FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | 2018-11-01 14:38:31 | THIS PERMIT IS NOW A STAND ALONE, MASTER 18091100 WAS | | | ISSUED SO THEY COULD DO THE SERVICE CHANGE WITH FPL. |
|