Plan Review Notes
Plan Review Notes For Permit 18091101
Permit Number 18091101
Review Stop G
Sequence Number 1
Notes
Date Text
2018-11-14 09:52:031) THERE ARE THREE DIFFERENT GAS DRAWINGS IN THIS
 PERMIT SUBMITTAL PACKAGE. REMOVE ALL OLD DOCUMENTS FROM
 THIS SUBMITTAL AND ORGANIZE THE DOCUMENTS INTO TWO
 COMPLETE SETS OF PLANS FOR REVIEW.FBC SEC. 107.2.1.
 2) SIZE THE EXISTING GAS LINE TO THE INTERIOR OF THE
 HOUSE AND SIZE THE EXISTING LINE TO THE POOL HEATER.
 3) SHOW THE DISTANCE FROM THE MEDIUM PRESSURE
 REGULATORS TO THE FURTHEST OUTLET ON THE LOW PRESSURE
 SIDE OF THE SYSTEM. I HAVE INCLUDED A COPY OF THE
 EXISTING GAS DRAWING IN THE PERMIT SUBMITTAL PACKAGE
 FOR REFERENCE.
 4) SHOW THE BTU LOAD OF THE EXISTING BBQ ON THE PLANS.
 FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
2018-11-01 14:38:31THIS PERMIT IS NOW A STAND ALONE, MASTER 18091100 WAS
 ISSUED SO THEY COULD DO THE SERVICE CHANGE WITH FPL.