| Date |
Text |
| 2018-11-15 11:24:36 | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | FAILED: |
| | |
| | 1) SHEET LS1.1 - THE CODE REFERENCE CITED IS 2014 FBC. |
| | PLEASE CORRECT TO THE CODE IN EFFECT WHICH IS THE 2017 |
| | FBC, |
| | |
| | 2) SHEET LS1.1 - THE CODE REFERENCE LISTS THE TYPE OF |
| | CONSTRICTION AS VB AND INDICATES THE BUILDING AS TWO |
| | STORIES NOT EXCEEDING 9,000 SF PER FLOOR. PLEASE CHECK |
| | THE BUILDING RECORD FOR ACCURACY AND VERIFY THE |
| | CONSTRUCTION TYPE CLASSIFICATION PER THE APPLICABLE |
| | CODE. PLEASE NOTE THE BUILDING APPEARS LARGER THAN |
| | INDICATED. |
| | |
| | 3) SHEET LS1.1 - THE PLAN IS NOT DIMENSIONED. PLEASE |
| | PROVIDE AT A MINIMUM, OVERALL DIMENSIONS PER FBC 107 |
| | AND TABULAR DATA FOR VERIFICATION OF THE DETERMINED |
| | OCCUPANT LOAD PER FBC T1004 |
| | |
| | 4) FBC ACCESSIBILITY - 202.4ALTERATIONS AFFECTING |
| | PRIMARY FUNCTION AREAS. PLEASE INDICATE THE LEVEL OF |
| | COMPLIANCE WITH ACCESSIBILITY CRITERIA. FOR EXAMPLE IS |
| | THE ENTRANCE ACCESSIBLE IS THERE ANY NEED TO PROVIDE |
| | ENHANCEMENTS PURSUANT TO THE FOREGOING SECTION. IT |
| | APPEARS THAT PART OF THE IMPROVEMENT COST RESULTS IN A |
| | BREAKROOM AREA THAT IS COMPLIANT. IF THERE IS NO NEED |
| | TO FURTHER EVALUATE OR PROVIDE ENHANCEMENTS PLEASE |
| | INDICATE SO. |
| | |
| | 5) SUITE NUMBER IDENTIFICATION. THE TITLE BLOCK |
| | INDICATE THE SPACE IS KNOWN AS OR TO BE KNOWN AS SUITE |
| | #100. THERE ARE MANY SUITE NUMBERS ON RECORD AT THIS |
| | ADDRESS HOWEVER NONE PREVIOUSLY AS 100. THE PERMIT |
| | APPLICATION PROGRAM CAN BE ADJUSTED TO IDENTIFY THE |
| | IMPROVEMENTS AT THIS SUITE NUMBER. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |
| | (561) 805-6710 |
| | [email protected] |
| | |