Plan Review Notes
Plan Review Notes For Permit 18091064
Permit Number 18091064
Review Stop P
Sequence Number 3
Notes
Date Text
2019-04-11 10:31:46APPROVED
 PROVISO
 1. SIGNED AND SEALED LETTERS (TWO COPIES) PROVIDING
 ROOF DRAIN CALCULATIONS SHALL BE SUBMITTED AS DEFERRED
 SUBMITTAL AS ALLOWED BY WPB FBC 107.3.4.1. APPROVED
 SUBMITTAL SHALL BE IN PLACE PRIOR TO THE FIRST
 INSPECTION.
 2. REFER TO RED LINED COMMENT ON P-2 SANITARY RISER AND
 P-1 FLOOR PLAN AT THE WATER CLOSETS. VENT SHALL RISE
 VERTICALLY ABOVE CENTER LINE OF HORIZONTAL DRAIN PER
 FBC PL 905.3 AND 905.4.
 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  