Plan Review Notes
Plan Review Notes For Permit 18091064
Permit Number 18091064
Review Stop P
Sequence Number 2
Notes
Date Text
2019-01-29 12:49:42CODES IN EFFECT:
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: DENIED
 1. EWH-1: PROVIDE ON DETAIL OF WATER HEATER THE THERMAL
 EXPANSION CONTROL DEVICE AND THE SIZE OF SAID DEVICE IN
 ACCORDANCE WITH FBC PL 607.3 PER WPB FPC 107.2.1.
 2. THE ADDED SERVICE SINK (TAG P-6) IS NOT SHOWN ON THE
 PLUMBING FLOOR PLAN PAGE P-1. PLEASE SHOW ON FLOOR
 PLANS P-1 AS WELL AS ON A-4 PER WPB FBC 107.2.1. THE
 PLUMBING FIXTURES AS SHOWN ON THE ARCHITECTURAL FLOOR
 PLAN A-4, PLUMBING FLOOR PLAN P-1 AND PLUMBING PLAN
 SHEET P-2 SHOULD ALL MATCH IN QUANTITY AND APPROXIMATE
 LOCATION/CONFIGURATION. PLEASE RECONCILE DRAWINGS PER
 WPB FBC 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 SINCERELY,