| 2019-01-29 12:49:42 | CODES IN EFFECT: |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 5TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | PLUMBING COMMENTS: DENIED |
| | 1. EWH-1: PROVIDE ON DETAIL OF WATER HEATER THE THERMAL |
| | EXPANSION CONTROL DEVICE AND THE SIZE OF SAID DEVICE IN |
| | ACCORDANCE WITH FBC PL 607.3 PER WPB FPC 107.2.1. |
| | 2. THE ADDED SERVICE SINK (TAG P-6) IS NOT SHOWN ON THE |
| | PLUMBING FLOOR PLAN PAGE P-1. PLEASE SHOW ON FLOOR |
| | PLANS P-1 AS WELL AS ON A-4 PER WPB FBC 107.2.1. THE |
| | PLUMBING FIXTURES AS SHOWN ON THE ARCHITECTURAL FLOOR |
| | PLAN A-4, PLUMBING FLOOR PLAN P-1 AND PLUMBING PLAN |
| | SHEET P-2 SHOULD ALL MATCH IN QUANTITY AND APPROXIMATE |
| | LOCATION/CONFIGURATION. PLEASE RECONCILE DRAWINGS PER |
| | WPB FBC 107.2.1. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |