| 2019-02-05 11:06:30 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18091064 |
| | 2/5/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DESIGN PROFESSIONAL OF RECORD SHALL PROVIDE A |
| | SHOP DRAWING STAMP ON THE PLASMA AIR IAQ CALCULATIONS |
| | AND SPEC SHEET FOR THE PLASMA AIR IONIZATION UNIT- |
| | SECTION 403.2 FBC M. |
| | |
| | 2) SECOND REQUEST FOR REQUIRED EXHAUST CALCULATIONS, |
| | EXHAUST SYSTEMS. AND AIR BALANCE CALCULATIONS. SHEETS |
| | M-1 & M-2: EXHAUST VENTILATION SYSTEMS ARE REQUIRED FOR |
| | THE ART, WOODWORKING, AND CLAY MIXING ROOMS IN |
| | ACCORDANCE WITH TABLE 403.3.1.1 FBC M. |
| | |
| | ART AND CLAY ROOMS RATES: 0.7 CFMS PER SF, |
| | |
| | WOODWORKING SHOP: 0.5 CFMS PER SF. |
| | |
| | REVISE THE PLANS TO SHOW THE REQUIRED SYSTEMS WITH |
| | DETAILS ON THE PLANS, PROVIDE EXHAUST AND AIR BALANCE |
| | CALCULATIONS, AND THE SEQUENCE OF OPERATIONS FOR THE |
| | SYSTEMS- 501.3.2 FBC M. PLEASE SEE FOOTNOTE G UNDER |
| | TABLE 403.3.1.1 WHICH LIMITS THE AMOUNT OF AIR THAT CAN |
| | BE RECIRCULATED FROM THE AREAS AND ROOMS BEING |
| | EXHAUSTED. |
| | |
| | 3) SECOND REQUEST FOR THE REQUIRED DUST COLLECTION |
| | SYSTEM IN THE SHOP. SHEETS M-1 & M-2: CLARIFY HOW DUST |
| | COLLECTION AND DISPOSAL WILL BE ACCOMPLISHED IN THE |
| | WOODWORKING SHOP. WILL A CENTRAL COLLECTION SYSTEM OR |
| | POINT OF USE COLLECTORS BE INSTALLED- SEE SECTION 511 |
| | FBC M AND PROVIDE DETAILS. |
| | |
| | 4) SECOND REQUEST FOR COMPLETE CLAY MIXER EXHAUST |
| | SYSTEM DETAILS AND SPECIFICATIONS. M-1 & M-2- CLAY |
| | MIXER EXHAUST SYSTEM: PROVIDE EQUIPMENT SCHEDULES ON |
| | THE PLAN FOR THE HOOD, FAN, DUCTWORK AND TERMINATION |
| | CAP, AND SUBMIT MANUFACTURER'S SPECS. C) SUBMIT FL. |
| | PRODUCT APPROVAL #11695 FOR THE ROOF EXHAUST FAN. D) |
| | INDICATE HOW REQUIRED MAKE UP AIR FOR THE EXHAUST HOOD |
| | IS BEING PROVIDED- SECTION 501.4 FBC M. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE CLAY MIXER, AND THE |
| | AF-1 & 2 AIR SCRUBBERS- SECTION 304.1 FBC M. |
| | |
| | 6) SHOW THE LOCATIONS OF ALL EXHAUST OUTLETS ON THE |
| | PLANS WITH CLEARANCE DISTANCE MEASURMENTS TO PROPERTY |
| | LINES, OPERABLE AND MECHANICAL OPENINGS INTO THE |
| | BUILDING, AND FROM ADJOING GRADES- SECTION 501.3.1 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |