| 2018-11-08 13:35:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | COMMENTS: |
| | 1. RE: PLAN SHEET P-2; PLUMBING FIXTURE |
| | SCHEDULE/REQUIREMENTS: |
| | A. BASED ON OCCUPANT LOAD OF 39+ FOR OCCUPANCY B, A |
| | SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |
| | B. EWH-1: REMARKS; HOW DOES REMARK ?OPTIONAL METAL |
| | HANDLE, VACUUM BREAKER? APPLY? PLEASE CLARIFY. |
| | C. P-4: DOES THE FAUCET SPOUT FOR THE SINK HAVE HOSE |
| | THREAD OUTLET? IF SO, A VACUUM BREAKER IS REQUIRED. |
| | PLEASE CLARIFY. |
| | D. P-4: IS ADA COMPLIANCE FOR THIS FIXTURE REQUIRED BY |
| | FBC ACC? IF SO, ARCHITECT SHALL NOTE AND ADDRESS ON THE |
| | ARCHITECTURAL PLANS PER WPB FBC 107.2.1. ADDITIONALLY, |
| | IT SHALL BE CONFIRMED THAT A PARALLEL APPROACH |
| | COMPLYING WITH FBC ACC 305 IS PERMITTED UNDER FBC ACC |
| | 606.2 PER WPB FBC 107.2.1. |
| | E. P-4: ADA COMPLIANT DRINKING FOUNTAIN SHALL BE NOTED |
| | AND ADDRESSED ON THE ARCHITECTURAL PLANS PER WPB FBC |
| | 107.2.1. |
| | 2. PLAN SHEET P-1 NOTE 4 CALLS FOR AN INSTA-HOT |
| | TANKLESS WATER HEATER AND A TEMPERATURE LIMITING DEVICE |
| | CONFORMING TO ASSE 1070 FOR EACH OF THE TOILET ROOMS. |
| | PLAN SHEET P-2 WATER RISER DIAGRAM SHOWS HOT WATER |
| | SUPPLIED TO THE LAVATORIES IN THE TOILET ROOMS BEING |
| | FURNISHED BY EWH-1 THROUGH THE TEMPERATURE LIMITING |
| | DEVICE. PLEASE CLARIFY. |
| | A. BEAR IN MIND THAT PER FBC PL 607.2, HOT WATER PIPING |
| | EXCEEDING 50? FROM THE HOT WATER SOURCE SHALL BE |
| | RECIRCULATED OR HEAT TRACED. |
| | 3. HOT WATER SHALL BE INSULATED IN ACCORDANCE WITH FBC |
| | EC C404.4. |
| | 4. EWH-1: PROVIDE DETAIL OF WATER HEATER SHOWING HEATER |
| | W/STORAGE CAPACITY, PIPING INCLUDING CW, HW, VALVING, |
| | THERMAL EXPANSION CONTROL DEVICE, T&P DISCHARGE |
| | (INCLUDING TERMINATION) AND WATER HEATER PAN AND DRAIN |
| | (INCLUDING TERMINATION) PER WPB FPC 107.2.1; COMPLY |
| | WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, |
| | 504.6, 504.7, 504.7.1 AND 504.7.2. |
| | 5. PLAN SHEET P-2 WATER RISER DIAGRAM NOTES NEW ?? HW |
| | CONNECTING TO EXISTING CW. PLEASE CLARIFY. |
| | 6. RE: PLAN SHEET P-2 SANITARY RISER DIAGRAM; |
| | A. PROVIDE VENT FOR EACH OF THE TWO WATER CLOSET |
| | FIXTURE DRAINS CONNECTING DIRECTLY TO THE BUILDING |
| | DRAIN PER FBC PL 909.1 TO COMPLY WITH THE REQUIREMENTS |
| | OF FBC PL CHAPTER 9. |
| | B. PROVIDE VENT FOR EACH OF THE THREE FIXTURE DRAINS |
| | FOR THE LAVATORIES AND DRINKING FOUNTAIN PER FBC PL |
| | 909.1 TO COMPLY WITH THE REQUIREMENTS OF FBC PL CHAPTER |
| | 9. |
| | 7. RE: PLAN SHEET P-2 MATERIAL NOTES: 22 11 16 DOMESTIC |
| | WATER. NOTE 2; CHANGE THE WORDS ?WATER PIPING BELOW |
| | GRADE SHALL BE? TO WORDS ?WATER SERVICE PIPING BELOW |
| | GRADE MAY BE?. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |