| 2018-11-09 15:57:34 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18091064 |
| | 11/8/2018 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M-1, & M-2: REFER TO SECTION 809.2 FBC EX AND |
| | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS |
| | AND SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS |
| | OF OUTDOOR AIR. |
| | |
| | 2) M-1 & M-2: PROVIDE THE MAKES AND MODELS AND COOLING |
| | AND HEATING CAPACITIES OF THE EXISTING RTU'S, AND |
| | INDICATE THE CFMS AT EACH DIFFUSER SHOWN ON THE PLAN. |
| | PLEASE NOTE THAT A TEST AND BALANCE REPORT MAY BE DUE |
| | AT FINAL INSPECTION |
| | |
| | 3) M-1 & M-2: EXHAUST VENTILATION SYSTEMS ARE REQUIRED |
| | FOR THE ART, WOODWORKING, AND CLAY MIXING ROOMS IN |
| | ACCORDANCE WITH TABLE 404.3.1.1 FBC M. |
| | |
| | ART AND CLAY ROOMS RATES: 0.7 CFMS PER SF, |
| | |
| | WOODWORKING SHOP: 0.5 CFMS PER SF. |
| | |
| | REVISE THE PLANS TO SHOW THE REQUIRED SYSTEMS WITH |
| | DETAILS ON THE PLANS, PROVIDE EXHAUST AND AIR BALANCE |
| | CALCULATIONS, AND THE SEQUENCE OF OPERATIONS FOR THE |
| | SYSTEMS- 501.3.2 FBC M. PLEASE SEE FOOTNOTE G UNDER |
| | TABLE 403.3.1.1 WHICH LIMITS THE AMOUNT OF AIR THAT CAN |
| | BE RECIRCULATED FROM THE AREAS AND ROOMS BEING |
| | EXHAUSTED. |
| | |
| | 4) M-1 & M-2: PROVIDE AN EQUIPMENT PLAN AND A |
| | CORRESPONDING EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 5) M-1 & M-2: CLARIFY HOW DUST COLLECTION AND DISPOSAL |
| | WILL BE ACCOMPLISHED IN THE WOODWORKING SHOP. WILL A |
| | CENTRAL COLLECTION SYSTEM OR POINT OF USE COLLECTORS BE |
| | INSTALLED- SEE SECTION 511 AND PROVIDE DETAILS. |
| | |
| | 6) M-1 & M-2- CLAY MIXER EXHAUST SYSTEM: A) PROVIDE |
| | DESIGN CRITERA- INDICATE WHICH STANDARD OR CODE USED, |
| | DESIGNED PER MANUFACTURER'S SPECIFICATIONS. . B) |
| | PROVIDE EQUIMENT SCHEDULES ON THE PLAN FOR THE HOOD, |
| | FAN, DUCTWORK AND TERMINATION CAP, AND SUBMIT |
| | MANUFACTURER'S SPECS. PLEASE NOTE THAT FL#11697 CALLED |
| | OUT IN THE NOTES IS A PRODUCT APPROVAL FOR A GRAVITY |
| | RELIEF CAP, HOWEVER THIS IS APPEARS TO BE A FORCED |
| | DRAFT SYSTEM. C) PROVIDE ENLARGED, DIMENSIONED FRONT |
| | AND PLAN VIEW DRAWINGS FOR THE EXHAUST HOOD SHOWING |
| | REQUIRED CLEARANCE DISTANCE MEASUREMENTS, THE TOTAL AND |
| | SEGMENTED LENGTHS OF THE EXHAUST DUCTWORK AND HOW THE |
| | HOOD, FAN, AND DUCTWORK WILL BE SUPPORTED. |
| | |
| | 7) M1 & M2- PRE-FAB KILN ROOM: SUBMIT A FL. PRODUCT |
| | APPROVAL OR STATE CERTIFICATION LETTER FOR THE ROOM TO |
| | VERIFY WIND LOAD COMPLIANCE AND IMPACT RATING OF THE |
| | STRUCTURE AND DOORS. CLARIFY IF THE AIROLITE LOUVERS |
| | ARE FACTORY OR FIELD INSTALLED AND SUBMIT THE FL. |
| | PRODUCT APPROVAL # 16746.1 THAT IS CALLED OUT ON THE |
| | PLAN. PLEASE NOTE THAT THE VENTILATION LOUVERS MUST |
| | ALSO BE COMPLIANT WITH THE AMCA 550 FOR WEATHER |
| | RESISTANCE PER SECTION 401.5. A) PROVIDE EQUIPMENT |
| | SCHEDULES ON THE PLAN FOR THE KILNS AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |