Plan Review Notes
Plan Review Notes For Permit 18091064
Permit Number 18091064
Review Stop M
Sequence Number 1
Notes
Date Text
2018-11-09 15:57:341ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18091064
 11/8/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-1, & M-2: REFER TO SECTION 809.2 FBC EX AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS
 AND SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF OUTDOOR AIR.
  
 2) M-1 & M-2: PROVIDE THE MAKES AND MODELS AND COOLING
 AND HEATING CAPACITIES OF THE EXISTING RTU'S, AND
 INDICATE THE CFMS AT EACH DIFFUSER SHOWN ON THE PLAN.
 PLEASE NOTE THAT A TEST AND BALANCE REPORT MAY BE DUE
 AT FINAL INSPECTION
  
 3) M-1 & M-2: EXHAUST VENTILATION SYSTEMS ARE REQUIRED
 FOR THE ART, WOODWORKING, AND CLAY MIXING ROOMS IN
 ACCORDANCE WITH TABLE 404.3.1.1 FBC M.
  
 ART AND CLAY ROOMS RATES: 0.7 CFMS PER SF,
  
 WOODWORKING SHOP: 0.5 CFMS PER SF.
  
 REVISE THE PLANS TO SHOW THE REQUIRED SYSTEMS WITH
 DETAILS ON THE PLANS, PROVIDE EXHAUST AND AIR BALANCE
 CALCULATIONS, AND THE SEQUENCE OF OPERATIONS FOR THE
 SYSTEMS- 501.3.2 FBC M. PLEASE SEE FOOTNOTE G UNDER
 TABLE 403.3.1.1 WHICH LIMITS THE AMOUNT OF AIR THAT CAN
 BE RECIRCULATED FROM THE AREAS AND ROOMS BEING
 EXHAUSTED.
  
 4) M-1 & M-2: PROVIDE AN EQUIPMENT PLAN AND A
 CORRESPONDING EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB.
  
 5) M-1 & M-2: CLARIFY HOW DUST COLLECTION AND DISPOSAL
 WILL BE ACCOMPLISHED IN THE WOODWORKING SHOP. WILL A
 CENTRAL COLLECTION SYSTEM OR POINT OF USE COLLECTORS BE
 INSTALLED- SEE SECTION 511 AND PROVIDE DETAILS.
  
 6) M-1 & M-2- CLAY MIXER EXHAUST SYSTEM: A) PROVIDE
 DESIGN CRITERA- INDICATE WHICH STANDARD OR CODE USED,
 DESIGNED PER MANUFACTURER'S SPECIFICATIONS. . B)
 PROVIDE EQUIMENT SCHEDULES ON THE PLAN FOR THE HOOD,
 FAN, DUCTWORK AND TERMINATION CAP, AND SUBMIT
 MANUFACTURER'S SPECS. PLEASE NOTE THAT FL#11697 CALLED
 OUT IN THE NOTES IS A PRODUCT APPROVAL FOR A GRAVITY
 RELIEF CAP, HOWEVER THIS IS APPEARS TO BE A FORCED
 DRAFT SYSTEM. C) PROVIDE ENLARGED, DIMENSIONED FRONT
 AND PLAN VIEW DRAWINGS FOR THE EXHAUST HOOD SHOWING
 REQUIRED CLEARANCE DISTANCE MEASUREMENTS, THE TOTAL AND
 SEGMENTED LENGTHS OF THE EXHAUST DUCTWORK AND HOW THE
 HOOD, FAN, AND DUCTWORK WILL BE SUPPORTED.
  
 7) M1 & M2- PRE-FAB KILN ROOM: SUBMIT A FL. PRODUCT
 APPROVAL OR STATE CERTIFICATION LETTER FOR THE ROOM TO
 VERIFY WIND LOAD COMPLIANCE AND IMPACT RATING OF THE
 STRUCTURE AND DOORS. CLARIFY IF THE AIROLITE LOUVERS
 ARE FACTORY OR FIELD INSTALLED AND SUBMIT THE FL.
 PRODUCT APPROVAL # 16746.1 THAT IS CALLED OUT ON THE
 PLAN. PLEASE NOTE THAT THE VENTILATION LOUVERS MUST
 ALSO BE COMPLIANT WITH THE AMCA 550 FOR WEATHER
 RESISTANCE PER SECTION 401.5. A) PROVIDE EQUIPMENT
 SCHEDULES ON THE PLAN FOR THE KILNS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2018-11-08 11:59:24DID NOT REVIEW WENT IN WRONG PERMIT#