2018-10-22 12:42:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW WIRE SIZE OF SERVICE OVERHEAD CONDUCTORS COMING
 OUT OF METER CAN TO POWER UTILITY. FBC 107.2.1
  
 2. ANNOTATE ON PLAN SIZE OF EXISTING OR NEWLY PROPOSED
 METER CANS FBC 107.2.1
  
 3. SERVICE RISER FOR "KILN" BUILDING SHOWS PANEL
 LABELED AS P-2 AS WELL AS PANEL SCHEDULE BUT PANEL IN
 BUILDING IS LABLED KB? PROVIDE CORRECTION FBC 107.2.1
  
 4. SERVICE RECEPTACLE REQUIRED WITH 50' OF SERVICE
 EQUIPMENT FOR BOTH BUILDINGS. NEC 210.64
  
 5. WORK AREA EXCEDES 50% OF OF BUILDING AREA, MAKING
 THIS A LEVEL 3 ALTERATION PER THE FBC EXISTING BUILDING
 CODE FOR MAIN BUILDING. CODE SUMMARY ON PLAN STATES
 THIS IS A LEVEL 2 ALTERATION. PROVIDE CORRECTION. FBC
 107.2.1 FBC EB 505.1
  
 6. A SYMBOL IN THE ELECTRICAL LEGEND SAYS "SPECIALTY
 RECEPTACLE" PLEASE PROVIDE UL/NRTL LISTING OF THESE
 RECEPTACLES FOR PRODUCT APPROVAL. .
  
 7. PROVIDE UL/NRTL LISTING FOR LIGHT FIXTURES FOR
 PRODUCT APPROVAL. NEC 90.7, NEC 110.2, NEC 110.3B, FBC
 107.2.1
  
 8. LIGHT NEEDED IN ELECTRICAL ROOM IN MAIN BUILDING.
 NEC 110.26D
  
 9. SHOW WINDOW RECEPTACLES REQUIRED IN MAIN BUILDING.
 NEC 210.62
  
 10. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR EXTERIOR
 SIGN. NEC 600.5; FBC EC 405.2.4
  
 11. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION, FOR EGRESS LIGHTINGFBC EC
 C405.2.5
  
 12. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING
 POWER ALLOWANCES PER THE FBC ENERGY CONSERVATION IN
 RELATION TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO
 COMPLY WITH CODE. FBC EC C405.5.1
  
 13. MORE THAN 8' OF UNPROTECTED SERVICE CONDUCTOR
 ENTERING KILN BUILDING FROM METER CAN TO MAIN BREAKER
 "KB"PANEL. NEC 230.70A
  
 14. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved