| 2018-10-22 12:42:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHOW WIRE SIZE OF SERVICE OVERHEAD CONDUCTORS COMING |
| | OUT OF METER CAN TO POWER UTILITY. FBC 107.2.1 |
| | |
| | 2. ANNOTATE ON PLAN SIZE OF EXISTING OR NEWLY PROPOSED |
| | METER CANS FBC 107.2.1 |
| | |
| | 3. SERVICE RISER FOR "KILN" BUILDING SHOWS PANEL |
| | LABELED AS P-2 AS WELL AS PANEL SCHEDULE BUT PANEL IN |
| | BUILDING IS LABLED KB? PROVIDE CORRECTION FBC 107.2.1 |
| | |
| | 4. SERVICE RECEPTACLE REQUIRED WITH 50' OF SERVICE |
| | EQUIPMENT FOR BOTH BUILDINGS. NEC 210.64 |
| | |
| | 5. WORK AREA EXCEDES 50% OF OF BUILDING AREA, MAKING |
| | THIS A LEVEL 3 ALTERATION PER THE FBC EXISTING BUILDING |
| | CODE FOR MAIN BUILDING. CODE SUMMARY ON PLAN STATES |
| | THIS IS A LEVEL 2 ALTERATION. PROVIDE CORRECTION. FBC |
| | 107.2.1 FBC EB 505.1 |
| | |
| | 6. A SYMBOL IN THE ELECTRICAL LEGEND SAYS "SPECIALTY |
| | RECEPTACLE" PLEASE PROVIDE UL/NRTL LISTING OF THESE |
| | RECEPTACLES FOR PRODUCT APPROVAL. . |
| | |
| | 7. PROVIDE UL/NRTL LISTING FOR LIGHT FIXTURES FOR |
| | PRODUCT APPROVAL. NEC 90.7, NEC 110.2, NEC 110.3B, FBC |
| | 107.2.1 |
| | |
| | 8. LIGHT NEEDED IN ELECTRICAL ROOM IN MAIN BUILDING. |
| | NEC 110.26D |
| | |
| | 9. SHOW WINDOW RECEPTACLES REQUIRED IN MAIN BUILDING. |
| | NEC 210.62 |
| | |
| | 10. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR EXTERIOR |
| | SIGN. NEC 600.5; FBC EC 405.2.4 |
| | |
| | 11. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN |
| | THE FBC ENERGY CONSERVATION, FOR EGRESS LIGHTINGFBC EC |
| | C405.2.5 |
| | |
| | 12. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING |
| | POWER ALLOWANCES PER THE FBC ENERGY CONSERVATION IN |
| | RELATION TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO |
| | COMPLY WITH CODE. FBC EC C405.5.1 |
| | |
| | 13. MORE THAN 8' OF UNPROTECTED SERVICE CONDUCTOR |
| | ENTERING KILN BUILDING FROM METER CAN TO MAIN BREAKER |
| | "KB"PANEL. NEC 230.70A |
| | |
| | 14. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |