Plan Review Notes
Plan Review Notes For Permit 18091064
Permit Number 18091064
Review Stop B
Sequence Number 1
Notes
Date Text
2018-11-21 14:50:14****CORRECTIONS****
 W.P.B. PERMIT: 18091064
 REVIEWED: NOVEMBER 20, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 [FBC AMENDED 105]PROVIDE SEPARATE PERMIT APPLICATION
 FOR THE MODULAR BUILDING. IT IS ON A SEPARATE PARCEL
 WITH A SEPARATE ADDRESS. THE PLANS CAN CONTAIN DRAWINGS
 FOR BOTH BUILDINGS AS PROVIDED, OR THEY CAN SPLIT UP.
  
 TWO REVIEWS ARE PROVIDED BELOW. THE FIRST IS FOR THE
 NEW STRUCTURE AND THE SECOND IS FOR THE EXISTING LEVEL
 3 ALTERATION.
  
 REVIEW FOR NEW STRUCTURE CONTAINING KILNS:
  
 1. [FBC AMENDED 107.3.5]
 LIST PROJECT DATA SEPARATE FOR EACH BUILDING.
 INCLUDE SPRINKLED OR NON-SPRINKLED
 CONSTRUCTION TYPE OF EACH BUILDING
 FIRE RESISTANCE RATING FOR NEW STRUCTURE
  
 2. [FBC 453.8.3.1]THE MINIMUM CONSTRUCTION TYPE FOR
 ONE- AND TWO-STORY PUBLIC EDUCATIONAL FACILITIES SHALL
 BE NONCOMBUSTIBLE TYPE I, II OR IV CONSTRUCTION OR
 BETTER.
  
 3. [FL STATUTE 553] IS THIS A MANUFACTURED BUILDING
 THAT HAS APPROVALS?
 IF SO PROVIDE COPY OF BUILDING INSTALLATION AND DETAILS
 OF FOUNDATION CONNECTION, AND ADA RAMP AS APPLICABLE TO
 THE NEW STRUCTURE.
 IF PRE-FAB MEANING PRE CAST WALL PANELS THAN PROVIDE
 THE PLANS WITH ENGINEERING OF HOW THE STRUCTURE MEETS
 REQUIREMENTS OF FBC CHAPTER 16.
 FOUNDATION PLAN, SECTION AND ROOF PLAN WILL ALSO BE
 NEEDED.
  
  
 4. [FBC 453.8.3.1]THE MINIMUM CONSTRUCTION TYPE FOR
 ONE- AND TWO-STORY PUBLIC EDUCATIONAL FACILITIES SHALL
 BE NONCOMBUSTIBLE TYPE I, II OR IV CONSTRUCTION OR
 BETTER.
  
 5. [FBC TABLE 602]SHOW FIRE SEPARATION DISTANCE BASED
 ON NEW STRUCTURE CONSTRUCTION TYPE AND FIRE RESITANCE
 REQUIREMENTS BASED ON TABLE 601.
 FIRE SEPARATION DISTANCE IS THE DISTANCE MEASURED FROM
 THE BUILDING FACE TO ONE OF THE FOLLOWING: 1) THE
 CLOSEST INTERIOR LOT LINE; 2) TO THE CENTERLINE OF A
 STREET, ALLEY OR PUBLIC WAY; OR 3) TO AN IMAGINARY LINE
 BETWEEN TWO BUILDINGS ON THE LOT. THE DISTANCE SHALL BE
 MEASURED AT RIGHT ANGLES FROM THE FACE OF THE WALL.
  
 6. [FBC TABLE 705.8]MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE
 OF OPENING PROTECTION.
 PROVIDE AMOUNT OF WALL OPENING BASED OFF OF FIRE
 SEPARATION FROM PREVIOUS COMMENTS AND ADJUST PLANS AS
 NEEDED TO MEET THE OPENING REQUIREMENTS FOR DOUBLE
 DOORS AND LOUVERS FACING EXISTING BUILDING.
  
 7. [FBC 453.7.4]COMMON FIRE ALARM. BUILDINGS WITHIN 60
 FEET
 (18,288 MM) OF EACH OTHER SHALL HAVE A COMMON FIRE
 ALARM
 SYSTEM.
 IS THERE AN EXISTING FIRE ALARM AND WILL THERE BE ONE
 IN THE NEW BUILDING?
  
 8. [FBC 453.12.1]CLASS A MATERIALS. ALL ROOFING
 MATERIALS SHALL BE
 LABELED CLASS A PER ASTM E108
 WHAT ROOF CLASS IS THE NEW BUILDING?
  
 9. [FL.STATUTE 553.842]PROVIDE PRODUCT APPROVAL FOR
 LOUVERS USED FOR HEAT VENTILATION, OR INDICATE THAT IT
 WILL BE DEFERRED.
  
 10. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 LEVEL 3 ALTERATION EXISTING BUILDING:
  
 11. [FBC AMENDED 107.3.5]
 LIST PROJECT DATA SEPARATE FOR EACH BUILDING.
 INCLUDE SPRINKLED OR NON-SPRINKLED
 CONSTRUCTION TYPE OF EACH BUILDING
 FIRE RESISTANCE RATING FOR EXISTING STRUCTURE
  
 12. [FBC TABLE 602]SHOW FIRE SEPARATION DISTANCE.
 IS THE NEW ROLL-UP TO BE FIRE RATED BASED ON
 SEPARATION?
 13. [FBC 705.2.3]COMBUSTIBLE PROJECTIONS. COMBUSTIBLE
 PROJECTIONS
 EXTENDING TO WITHIN 5 FEET (1524 MM) OF THE LINE USED
 TO DETERMINE THE FIRE SEPARATION DISTANCE SHALL BE OF
 NOT
 LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION.
 IS AWNING COMBUSTIBLE?
  
 14 [FBC TABLE 705.2]MINIMUM DISTANCE OF PROJECTION.
 REVIEW THE PROPOSED AWNING FOR FIRE SEPARTION.
 IS THE AWNING CROSSING THE PROPERTY LINES?
 THE PARCELS WOULD NEED UNITY OF TITLE IF STRUCTURES ARE
 CROSSING OVER LINES. PROVIDE SURVEY TO SHOW EXISTING
 PROPERTY LINES, EASEMENTS AND PROPOSED/EXISTING
 STRUCTURES WITHIN.
  
 15. [FBC AMENDED 107.3.5]SHEET A-4, A-6 AND A-7 NEED
 CO-ORDINATION OF CALL OUTS AND DETAILS. SHEET A-4 CALL
 -OUT 1/A-6 AT BATHROOM IS OK TO FIND WALL SECTION ON
 SHEET A-6, BUT MAY NEED TO ADD WALL CALL OUT TO OTHER
 NEW WALLS AS WELL. ALL OTHER CALL OUTS ARE EITHER
 MISSING OR DON?T CORRESPOND TO THE CORRECT DETAIL.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  