| 2018-11-21 14:50:14 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18091064 |
| | REVIEWED: NOVEMBER 20, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | [FBC AMENDED 105]PROVIDE SEPARATE PERMIT APPLICATION |
| | FOR THE MODULAR BUILDING. IT IS ON A SEPARATE PARCEL |
| | WITH A SEPARATE ADDRESS. THE PLANS CAN CONTAIN DRAWINGS |
| | FOR BOTH BUILDINGS AS PROVIDED, OR THEY CAN SPLIT UP. |
| | |
| | TWO REVIEWS ARE PROVIDED BELOW. THE FIRST IS FOR THE |
| | NEW STRUCTURE AND THE SECOND IS FOR THE EXISTING LEVEL |
| | 3 ALTERATION. |
| | |
| | REVIEW FOR NEW STRUCTURE CONTAINING KILNS: |
| | |
| | 1. [FBC AMENDED 107.3.5] |
| | LIST PROJECT DATA SEPARATE FOR EACH BUILDING. |
| | INCLUDE SPRINKLED OR NON-SPRINKLED |
| | CONSTRUCTION TYPE OF EACH BUILDING |
| | FIRE RESISTANCE RATING FOR NEW STRUCTURE |
| | |
| | 2. [FBC 453.8.3.1]THE MINIMUM CONSTRUCTION TYPE FOR |
| | ONE- AND TWO-STORY PUBLIC EDUCATIONAL FACILITIES SHALL |
| | BE NONCOMBUSTIBLE TYPE I, II OR IV CONSTRUCTION OR |
| | BETTER. |
| | |
| | 3. [FL STATUTE 553] IS THIS A MANUFACTURED BUILDING |
| | THAT HAS APPROVALS? |
| | IF SO PROVIDE COPY OF BUILDING INSTALLATION AND DETAILS |
| | OF FOUNDATION CONNECTION, AND ADA RAMP AS APPLICABLE TO |
| | THE NEW STRUCTURE. |
| | IF PRE-FAB MEANING PRE CAST WALL PANELS THAN PROVIDE |
| | THE PLANS WITH ENGINEERING OF HOW THE STRUCTURE MEETS |
| | REQUIREMENTS OF FBC CHAPTER 16. |
| | FOUNDATION PLAN, SECTION AND ROOF PLAN WILL ALSO BE |
| | NEEDED. |
| | |
| | |
| | 4. [FBC 453.8.3.1]THE MINIMUM CONSTRUCTION TYPE FOR |
| | ONE- AND TWO-STORY PUBLIC EDUCATIONAL FACILITIES SHALL |
| | BE NONCOMBUSTIBLE TYPE I, II OR IV CONSTRUCTION OR |
| | BETTER. |
| | |
| | 5. [FBC TABLE 602]SHOW FIRE SEPARATION DISTANCE BASED |
| | ON NEW STRUCTURE CONSTRUCTION TYPE AND FIRE RESITANCE |
| | REQUIREMENTS BASED ON TABLE 601. |
| | FIRE SEPARATION DISTANCE IS THE DISTANCE MEASURED FROM |
| | THE BUILDING FACE TO ONE OF THE FOLLOWING: 1) THE |
| | CLOSEST INTERIOR LOT LINE; 2) TO THE CENTERLINE OF A |
| | STREET, ALLEY OR PUBLIC WAY; OR 3) TO AN IMAGINARY LINE |
| | BETWEEN TWO BUILDINGS ON THE LOT. THE DISTANCE SHALL BE |
| | MEASURED AT RIGHT ANGLES FROM THE FACE OF THE WALL. |
| | |
| | 6. [FBC TABLE 705.8]MAXIMUM AREA OF EXTERIOR WALL |
| | OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE |
| | OF OPENING PROTECTION. |
| | PROVIDE AMOUNT OF WALL OPENING BASED OFF OF FIRE |
| | SEPARATION FROM PREVIOUS COMMENTS AND ADJUST PLANS AS |
| | NEEDED TO MEET THE OPENING REQUIREMENTS FOR DOUBLE |
| | DOORS AND LOUVERS FACING EXISTING BUILDING. |
| | |
| | 7. [FBC 453.7.4]COMMON FIRE ALARM. BUILDINGS WITHIN 60 |
| | FEET |
| | (18,288 MM) OF EACH OTHER SHALL HAVE A COMMON FIRE |
| | ALARM |
| | SYSTEM. |
| | IS THERE AN EXISTING FIRE ALARM AND WILL THERE BE ONE |
| | IN THE NEW BUILDING? |
| | |
| | 8. [FBC 453.12.1]CLASS A MATERIALS. ALL ROOFING |
| | MATERIALS SHALL BE |
| | LABELED CLASS A PER ASTM E108 |
| | WHAT ROOF CLASS IS THE NEW BUILDING? |
| | |
| | 9. [FL.STATUTE 553.842]PROVIDE PRODUCT APPROVAL FOR |
| | LOUVERS USED FOR HEAT VENTILATION, OR INDICATE THAT IT |
| | WILL BE DEFERRED. |
| | |
| | 10. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS |
| | FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | LEVEL 3 ALTERATION EXISTING BUILDING: |
| | |
| | 11. [FBC AMENDED 107.3.5] |
| | LIST PROJECT DATA SEPARATE FOR EACH BUILDING. |
| | INCLUDE SPRINKLED OR NON-SPRINKLED |
| | CONSTRUCTION TYPE OF EACH BUILDING |
| | FIRE RESISTANCE RATING FOR EXISTING STRUCTURE |
| | |
| | 12. [FBC TABLE 602]SHOW FIRE SEPARATION DISTANCE. |
| | IS THE NEW ROLL-UP TO BE FIRE RATED BASED ON |
| | SEPARATION? |
| | 13. [FBC 705.2.3]COMBUSTIBLE PROJECTIONS. COMBUSTIBLE |
| | PROJECTIONS |
| | EXTENDING TO WITHIN 5 FEET (1524 MM) OF THE LINE USED |
| | TO DETERMINE THE FIRE SEPARATION DISTANCE SHALL BE OF |
| | NOT |
| | LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. |
| | IS AWNING COMBUSTIBLE? |
| | |
| | 14 [FBC TABLE 705.2]MINIMUM DISTANCE OF PROJECTION. |
| | REVIEW THE PROPOSED AWNING FOR FIRE SEPARTION. |
| | IS THE AWNING CROSSING THE PROPERTY LINES? |
| | THE PARCELS WOULD NEED UNITY OF TITLE IF STRUCTURES ARE |
| | CROSSING OVER LINES. PROVIDE SURVEY TO SHOW EXISTING |
| | PROPERTY LINES, EASEMENTS AND PROPOSED/EXISTING |
| | STRUCTURES WITHIN. |
| | |
| | 15. [FBC AMENDED 107.3.5]SHEET A-4, A-6 AND A-7 NEED |
| | CO-ORDINATION OF CALL OUTS AND DETAILS. SHEET A-4 CALL |
| | -OUT 1/A-6 AT BATHROOM IS OK TO FIND WALL SECTION ON |
| | SHEET A-6, BUT MAY NEED TO ADD WALL CALL OUT TO OTHER |
| | NEW WALLS AS WELL. ALL OTHER CALL OUTS ARE EITHER |
| | MISSING OR DON?T CORRESPOND TO THE CORRECT DETAIL. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |