Plan Review Notes
Plan Review Notes For Permit 18091063
Permit Number 18091063
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-27 10:01:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN MUST BE SIGNED AND 2 COPIES OF PLAN MUST BE
 SUBMITTED. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
  
 2. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1
  
 3. SHOW BREAKER SIZE IN METER/MAIN COMBO FOR SUB-PANEL.
 SHOW WIRE SIZE TO SUB-PANEL. NEC 215.5, 230, 250.50,
 250.94, 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  