Plan Review Notes
Plan Review Notes For Permit 18090994
Permit Number 18090994
Review Stop P
Sequence Number 1
Notes
Date Text
2018-10-18 09:37:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS:
  
 1. RE: A-3; HOT WATER REQUIRED PER FBC PL 607.1.
 PROVIDE TEMPERED WATER TO LAVATORY IN ACCORDANCE WITH
 FBC PL 416.5, 607.1.1 AND 607.1.2.
 A. SHOW LOCATION OF WATER HEATER ON PLAN. PROVIDE WATER
 HEATER SCHEDULE PER WPB FPC 107.3.5.1.3 (5). IF A
 STORAGE TYPE WATER HEATER IS SPECIFIED THEN INCLUDE
 THERMAL EXPANSION CONTROL DEVICE, T&P DISCHARGE(
 INCLUDING TERMINATION) AND WATER HEATER PAN AND DRAIN
 (INCLUDING TERMINATION)PER WPB FPC 107.2.1; COMPLY WITH
 FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5,
 504.6, 504.7, 504.7.1 AND 504.7.2.
 B. PROVIDE SPEC FOR APPROVED WATER-TEMPERATURE LIMITING
 DEVICE THAT CONFORMS TO ASSE 1070 OR CSA B125.3 FOR
 LAVATORY.
 2. RE: A-3; PLUMBING RISER. SHOW CONNECTION TO SANITARY
 STACK AT WET COLUMN.
 3. RE: A-3; PLUMBING LAYOUT. SHOW CONNECTION TO
 SANITARY STACK AND LABEL AT WET COLUMN; ELIMINATE
 CONNECTION OR REFERENCE TO BUILDING SEWER.
 4. RE: A-3; PLUMBING NOTE 16. THE NOTE ALLUDES TO GAS
 PIPING. THERE IS NO PLAN SHOWING GAS PIPING AND NO
 REVIEW HAS BEEN MADE. IF THERE IS GAS PIPING, AN
 APPLICATION FOR GAS PERMIT MUST BE SUBMITTED ALONG WITH
 PLANS COMPLYING WITH FBC FG. IF THERE IS NO GAS PIPING
 THEN PLEASE REMOVE THE NOTE PER WPB FBC 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715