| 2018-10-18 09:37:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | PLUMBING COMMENTS: |
| | |
| | 1. RE: A-3; HOT WATER REQUIRED PER FBC PL 607.1. |
| | PROVIDE TEMPERED WATER TO LAVATORY IN ACCORDANCE WITH |
| | FBC PL 416.5, 607.1.1 AND 607.1.2. |
| | A. SHOW LOCATION OF WATER HEATER ON PLAN. PROVIDE WATER |
| | HEATER SCHEDULE PER WPB FPC 107.3.5.1.3 (5). IF A |
| | STORAGE TYPE WATER HEATER IS SPECIFIED THEN INCLUDE |
| | THERMAL EXPANSION CONTROL DEVICE, T&P DISCHARGE( |
| | INCLUDING TERMINATION) AND WATER HEATER PAN AND DRAIN |
| | (INCLUDING TERMINATION)PER WPB FPC 107.2.1; COMPLY WITH |
| | FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, |
| | 504.6, 504.7, 504.7.1 AND 504.7.2. |
| | B. PROVIDE SPEC FOR APPROVED WATER-TEMPERATURE LIMITING |
| | DEVICE THAT CONFORMS TO ASSE 1070 OR CSA B125.3 FOR |
| | LAVATORY. |
| | 2. RE: A-3; PLUMBING RISER. SHOW CONNECTION TO SANITARY |
| | STACK AT WET COLUMN. |
| | 3. RE: A-3; PLUMBING LAYOUT. SHOW CONNECTION TO |
| | SANITARY STACK AND LABEL AT WET COLUMN; ELIMINATE |
| | CONNECTION OR REFERENCE TO BUILDING SEWER. |
| | 4. RE: A-3; PLUMBING NOTE 16. THE NOTE ALLUDES TO GAS |
| | PIPING. THERE IS NO PLAN SHOWING GAS PIPING AND NO |
| | REVIEW HAS BEEN MADE. IF THERE IS GAS PIPING, AN |
| | APPLICATION FOR GAS PERMIT MUST BE SUBMITTED ALONG WITH |
| | PLANS COMPLYING WITH FBC FG. IF THERE IS NO GAS PIPING |
| | THEN PLEASE REMOVE THE NOTE PER WPB FBC 107.2.1. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |