| 2018-10-12 15:55:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090994 |
| | 10/12/2018 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM- SECTION C403.2.1 FBC-17 EC. |
| | |
| | 2) THE PERSON WHO PREPARED THE ENERGY/GAUGE CALCULATION |
| | FORM AND THE BUILDING'S OWNER SHALL EACH SIGN AND DATE |
| | THE FORM ON THE CERTIFICATIONS PAGE- SECTION C103.1.1.2 |
| | FBC EC |
| | |
| | 3) SHEET A-3: PROVIDE MINIMUM VENTILATION CALCULATIONS |
| | FOR ALL ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 |
| | MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE |
| | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE |
| | THAT THE AC EQUIPMENT SCHEDULE IS INDICATING 440 CFMS |
| | OF OUTSIDE AIR IS BEING PROVIDED WHICH SEEMS TO BE |
| | EXCESSIVE FOR THIS 1066 SF. OFFICE SPACE. |
| | |
| | 4) A-3: THE AC EQUIPMENT SCHEDULE INDICATES COOLING AND |
| | HEATING CAPCITIES FOR THE SYSTEM THAT DON'T MATCH THE |
| | COMPLIANCE DATA IN THE ENERGY/GAUGE FORM. THE SCHEDULE |
| | INDICATES COOLING AT 30,136 BTUH HOWEVER THE ENERGY |
| | CALCS INDICATE 34,000 BTUH. |
| | |
| | 5) THE AC EQUIPMENT SCHEDULE INDICATES THE TOTAL SUPPLY |
| | AIR FOR THE SYSTEM IS 671 CFMS, HOWEVER THE PLAN |
| | INDICATES 950 CFMS- PLEASE CORRECT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |