Plan Review Notes
Plan Review Notes For Permit 18090994
Permit Number 18090994
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-30 14:14:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090994
 ADD: 2465 MERCER AVE., SUITE:A-205
 CONT: SEARCH CONSTRUCTION
 TEL: 561-346-8191
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 30/ 2018
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED MISSING FROM THE
 FLOOR/ LIFE SAFETY PLAN. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS:
 1A) THE MINIMUM BUILDING TYPE? 2017 FBC-B TABLE 504.3 &
 504.4.
 1B) STORIES THIS BUILDING HAS? 2017 FBC-B TABLE 504.3 &
 504.4
 1C) THE ACTUAL SQUARE FOOTAGE FOR EACH STORY? 2017
 FBC-B TABLE 504.3 & 504.4
 1D) IS THE BUILDING FIRE SPRINKLERED? 2017 FBC-B TABLE
 504.3 & 504.4
 1E) SQUARE FOOTAGE OF THE TENANT SPACE? 2017 FBC-B
 TABLE 504.3 & 504.4
  
 2) THE PLANS DOES NOT INDICATE IF THE LOCATION OF THE
 WATER CLOSET IS A NEW LOCATION REQUIRING A NEW FLOOR
 PENETRATION AND FIRE RATED FLOOR ASSEMBLIES PER 2017
 FBC-B 714.4 HORIZONTAL ASSEMBLIES. PENETRATIONS OF A
 FIRE-RESISTANCE-RATED FLOOR, FLOOR/CEILING ASSEMBLY OR
 THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT
 REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1
 THROUGH 714.4.4.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  