| 2018-10-30 14:14:40 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18090994 |
| | ADD: 2465 MERCER AVE., SUITE:A-205 |
| | CONT: SEARCH CONSTRUCTION |
| | TEL: 561-346-8191 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. OCT. 30/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) ADDITIONAL INFORMATION IS REQUIRED MISSING FROM THE |
| | FLOOR/ LIFE SAFETY PLAN. 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE |
| | DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE |
| | FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: |
| | 1A) THE MINIMUM BUILDING TYPE? 2017 FBC-B TABLE 504.3 & |
| | 504.4. |
| | 1B) STORIES THIS BUILDING HAS? 2017 FBC-B TABLE 504.3 & |
| | 504.4 |
| | 1C) THE ACTUAL SQUARE FOOTAGE FOR EACH STORY? 2017 |
| | FBC-B TABLE 504.3 & 504.4 |
| | 1D) IS THE BUILDING FIRE SPRINKLERED? 2017 FBC-B TABLE |
| | 504.3 & 504.4 |
| | 1E) SQUARE FOOTAGE OF THE TENANT SPACE? 2017 FBC-B |
| | TABLE 504.3 & 504.4 |
| | |
| | 2) THE PLANS DOES NOT INDICATE IF THE LOCATION OF THE |
| | WATER CLOSET IS A NEW LOCATION REQUIRING A NEW FLOOR |
| | PENETRATION AND FIRE RATED FLOOR ASSEMBLIES PER 2017 |
| | FBC-B 714.4 HORIZONTAL ASSEMBLIES. PENETRATIONS OF A |
| | FIRE-RESISTANCE-RATED FLOOR, FLOOR/CEILING ASSEMBLY OR |
| | THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT |
| | REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1 |
| | SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1 |
| | THROUGH 714.4.4. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |