| 2018-09-25 14:52:05 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS | | | REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE | | | DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE. | | | SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED. | | | ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION | | | SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE | | | REQUIRED INFORMATION IS PROVIDED. | | | NOTE: IT LOOKS LIKE THE PROPOSED ACCORDION SHUTTERS ARE | | | GOING TO BE INSTALLED ON THE SECOND FLOOR. I BELIEVE | | | THE SECOND FLOOR OF THESE HOUSES ARE WOOD FRAMED. TAKE | | | THIS INTO CONSIDERATION WHEN COMPLETING THE | | | INSTALLATION SCHEDULE TO AVOID CONFLICTS/DELAYS. | | | PROPOSED INSTALLATION WILL BE REVIEWED WHEN COMPLETE | | | SHUTTERS INSTALLATION SCHEDULE IS PROVIDED. | | | | | | 2- ACCORDING TO KEY PLAN SUBMITTED, IT LOOKS LIKE SOME | | | OPENINGS ARE LOCATED IN THE END ZONE #5. USE THE | | | CORRESPONDING DESIGN PRESSURES WHEN COMPLETING THE | | | INSTALLATION SCHEDULE. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|