2018-09-25 14:52:05RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED.
 NOTE: IT LOOKS LIKE THE PROPOSED ACCORDION SHUTTERS ARE
 GOING TO BE INSTALLED ON THE SECOND FLOOR. I BELIEVE
 THE SECOND FLOOR OF THESE HOUSES ARE WOOD FRAMED. TAKE
 THIS INTO CONSIDERATION WHEN COMPLETING THE
 INSTALLATION SCHEDULE TO AVOID CONFLICTS/DELAYS.
 PROPOSED INSTALLATION WILL BE REVIEWED WHEN COMPLETE
 SHUTTERS INSTALLATION SCHEDULE IS PROVIDED.
  
 2- ACCORDING TO KEY PLAN SUBMITTED, IT LOOKS LIKE SOME
 OPENINGS ARE LOCATED IN THE END ZONE #5. USE THE
 CORRESPONDING DESIGN PRESSURES WHEN COMPLETING THE
 INSTALLATION SCHEDULE. SEC. R301.1 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  